Table of Contents Table of Contents ............. 2 Tables Note to the User ............3 Table 1—General Piping Information ..... 4 General Piping Information ........4 Table 2—Copper Finned Tube Base Board Specific Frequently Asked Questions ........5 Information ............ 4 Definitions &...
If they are fittings or pipe sizes and materials being used that are not covered in this manual please contact Rinnai for further information. This is not a product installation manual, please refer to the installation/ operation manual that accompanied the product for specific information regarding installation and safety.
Then the maximum flow rate and available pump head should be used to determine if the boiler is suitable for installation without the addition of a Rinnai low loss header plumbing kit (part number 804000061). It is the responsibility of the contractor or engineer to calculate the pressure drop through the system and the required flow...
7. If the E50C boiler is installed in a system with zone valves and the constant recirculation function is activated, then a differential pressure bypass valve or a low loss header plumbing kit is required to be installed.
Definitions Single Heating Loop System A single heating loop system can be considered any of the following piping – arrangements: series loop, one pipe with diverter tees, or two pipe reverse return. These types of systems will have only a single room thermostat centrally located that controls the boiler. Zoned System A zoned system is a heating system that utilizes multiple zones which are individually controlled by –...
Calculating Zone Flow Rates Notice Zones should be balanced using balancing valves to ensure the correct output (flow rate) of each zone. Use the hydronic formula to calculate the flow rate for each zone. The constant 500 is based on the use of water as the heat transfer fluid in the system, where 8.33 pounds/gallon of water x 60 minutes per hour = 500.
ATTENTION Rinnai strongly recommends the use of full port ball valve zone valves; these valves provide a lower pressure drop than a gate valve type zone valve. The lower pressure drop will allow for longer loop lengths and better flow through the zones.
Page 9
The single zone serial flow system in Drawing 1 consists of the following copper fittings and tubing and is designed to operate at 4.0 gpm flow rate at 170°F supply temperature. (Below is a list of each type of component and quantity of the components contained in drawing 1.) a.
Notice Rinnai recommends that the tee fittings for the pressure relief valve and the boiler drain are placed directly below the boiler as shown in the drawing above. These fittings then can be utilized as connection points for taking a differential pressure in the...
Drawing 4 *Rinnai strongly recommends the use of full port ball valve type zone valves to allow for the best performance of the boiler and system. When piped as shown in the drawing above, the air handler cannot have an internal pump.
One Pipe System using Diverter Tee (Mono Flow Tee) Greater than 4.6 feet of head pressure drop Low loss header plumbing kit required (Low Loss Header Plumbing kit part number: 804000061) Drawing 5 Multiple Zone Circulators with Low Loss Header Plumbing Kit Circulators used for Zoning Low loss header plumbing kit required (Low Loss Header Plumbing kit part number: 804000061)
Single Serial Flow Loop (zone) Greater than 4.6 feet of head pressure drop Low loss header plumbing kit required (Low Loss Header Plumbing kit part number: 804000061) Drawing 7...
Radiant Manifold System Low loss header plumbing kit required (Low Loss Header Plumbing kit part number: 804000061) Drawing 8 Drawing 8 If the boiler is installed in a system with zone valves and the constant recirculation function is activated then a differential pressure bypass valve or a low loss header plumbing kit is required to be installed.
Appendix D Example – Calculating the Equivalent Length (Alternate Method) Drawing 9 The single zone serial flow system in Drawing 9 consists of the following copper fittings and tubing and is designed to operate at 4.0 gpm flow rate at 170°F supply temperature. (Below is a list of each type of component and quantity of the components contained in drawing 9.) a.
Page 19
1) Calculate the pressure drop of the additional fittings d and e by using the C value of fittings from Table 4 and for the values of from Appendix B table 7. For this case both fittings d and e have the same C value so account for this in step 5: 2) Convert the pressure drop calculated in step 1 from psi to feet of head (1psi=2.3 feet of head)
Page 20
4) Add up the number of each type of fitting and multiply the number of each type of fittings by its equivalent length see Appendix A table 3 for equivalent lengths of fittings. Then add up the equivalent lengths of the fittings using Worksheet 1 for you calculation;...
Appendix E Diverter Tee Equivalent length Calculation Calculating the resistance of a diverter tee loop R1 = radiation equivalent length R2 = vertical rise equivalent length and elbow equivalent length R3 = vertical rise equivalent length and elbow equivalent length R4 = main loop equivalent length and standard Tee fitting equivalent length R5 = Diverter tee Example...