Technical Data
IMPORTANT All inputs and outputs must be Class 2 (100 VA) wiring.
Power supply
Power supply
Rated voltage
Frequency
Transformer
Inputs
Sensors
Combination Temperature/Humidity
Sensor (e.g., QFM2160U)
Dry Bulb Temperature Sensor Type II NTC
10K (e.g., QAM2030.010) or 0-10 Vdc
Demand Control Ventilation (DCV) Sensor
(e.g., QPA2000)
Detailed technical data are available in the documentation of the corresponding sensor.
Digital inputs
24 Vac power supply
Frequency
Wiring
Outputs
Actuator (e.g., GCA151.1P)
Actuator Signal
Actuator Input Resistance
VFD Signal
Relay contact ratings
Detailed technical data are available in the documentation of the corresponding actuator.
10
Siemens
Smart Infrastructure
24Vac (20 Vac~30 Vac)
50/60 Hz
Max. 100 VA
5-wire (18, 20, or 22 AWG cable) connection
2-wire (18, 20, or 22 AWG cable) connection
3- wire (18, 20, or 22 AWG cable)
0 to 10 Vdc control signal
24Vac (20 Vac~30 Vac)
50/60 Hz
1-wire 24 Vac + common GND
4-wire (18 AWG)
2 to 10 Vdc
100K ohm
0 to 10 Vdc
30 Vac (maximum power from class 2 input
only), 3A run, and 7.5A inrush
A6V11681604_enUS_c
03/27/2023