INSTALLATION, OPERATION & MAINTENACE DATA SHEET
(EPL-EMG-CM SERIES COMPACT FLUORESCENT EMERGENCY FACTORY SEALED LIGHTING FIXTURES)
IMPORTANT SAFEGUARDS – READ AND
FOLLOW ALL SAFETY INSTRUCTIONS.
NOTE: LAMP MUST BE INSTALLED BEFORE OPERATING
Remove globe assembly, unpack bulb and insert into socket.
See installation instruction sections 4 & 5 for removal of globe assembly.
NOTE: Read this sheet carefully before beginning installation.
• Do not use this equipment for other than the intended use as specified on equipment
nameplate.
WARNING:
Turn off the supplying circuit before beginning installation, or
performing any maintenance including re-lamping.
• Do not install near gas or electric heaters.
• Do not attempt to service battery. The emergency ballast contains a sealed, no-
Maintenance battery. Contact manufacturer for information on replacements.
• Batteries must be recycled or disposed of properly.
• Servicing should be performed by qualified service personnel.
• The use of accessory equipment not recommended by the manufacturer can
cause an unsafe condition
• Equipment should be mounted in locations and at heights were it will not readily be
subjected to tampering by unauthorized personnel.
• The emergency ballast is for use with quad pin compact fluorescent lamps only.

INSTALLATION:

Important Note:
1. All installations must comply with the applicable local and/or National Electrical
Code.
2. Before installing, check the fixture nameplate to be sure you have the correct
fixture.
3. Verify ground continuity in the electrical system.
4. The emergency ballast must be connected to an unswitched power source.
5. Refer to nameplate for specific ambient and supply wire temperature rating.
EPL-EMG-CM-42W

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the EPL-EMG-CM-42W and is the answer not in the manual?

Questions and answers

Summary of Contents for Larson Electronics EPL-EMG-CM-42W

  • Page 1 EPL-EMG-CM-42W INSTALLATION, OPERATION & MAINTENACE DATA SHEET (EPL-EMG-CM SERIES COMPACT FLUORESCENT EMERGENCY FACTORY SEALED LIGHTING FIXTURES) IMPORTANT SAFEGUARDS – READ AND FOLLOW ALL SAFETY INSTRUCTIONS. NOTE: LAMP MUST BE INSTALLED BEFORE OPERATING Remove globe assembly, unpack bulb and insert into socket.
  • Page 2 Following steps required for installation - 1. Install unit’s mounting accessory per instructions supplied with the mount. 2. Install unit’s pushbutton test station (purchased separately) per instructions supplied with station. Station must be wired to fixture mount to provide a method of disconnecting the supply source from the unit.
  • Page 3 test station and observe that the lamp operates. 8. To install optional guard (E) loosen the four screws on the bottom of the globe support ring, slip the guard over the screws and rotate to the locked position. Tighten the screws firmly. NOTE: Emergency ballast must be charged for 36 hrs before running test(s).

Table of Contents