Summary of Contents for Larson Electronics VFD-1P-220.240-1HP-7A-DCM
Page 1
VFD-1P-220.240-1HP-7A-DCM VFD-1P-220.240-1HP-7A-DCM User Manual (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 1 of 52...
Page 2
CAUTION age to equipment. (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 2 of 52...
Page 3
Since overall leakage current of this equipment may be bigger than 3.5mA, for safety's sake, this equipment and its associated motor must be well grounded so as to avoid risk of electric shock; (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 3 of 52...
Page 4
If auto tuning is required, be careful of personal injury when motor is running. Risk of accident; CAUTION ² Do not change the defaults of parameters. Risk of devices damage. (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 4 of 52...
Page 5
All pluggable components can be inserted or pulled out only when power has been turned off; ² Set and check the parameters again after the VFD is replaced. (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 5 of 52...
Page 6
Fig.3-2 to ensure good heat dissipation. Fan exhaust More than 200mm More than 200mm Figure 3-1 Mounting space and distance Figure 3-2 Mounting of multiple VFDs (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 6 of 52...
Page 8
Fault relay output DC Ammeter 4-20mACurrent signal High-speed pulse output +10V 0~10V Open collector output 0~10V/4~20mA Standard RS485 communication port 485+ 485- Figure 4-2 Basic Wiring Diagram (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 8 of 52...
Page 9
Starting capacitor Main winding 220VAC Figure 4-4 Operation mode: Internal wiring of motor with single capacitor (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 9 of 52...
Page 10
Internal wiring of single phase motor with double capacitors is as below: Running capacitor Centrifugal switch Starting capacitor 220VAC Main winding Figure 4-6 Internal wiring of motor with double capacitors (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 10 of 52...
Page 11
After removing the capacitors from above motors, remain 4 main and secondary winding terminals as below: Figure 4-8 Main and secondary winding of motor (After removing the capacitors) (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 11 of 52...
Page 12
Motor reverse can’t be completed through parameter setting of VFD or change any two phase wirings, motor reverse wiring must be as below: (PB) 220VAC Figure 4-10 Reverse wiring between VFD (<=0.75Kw) and motor (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 12 of 52...
Page 13
4.3.3 Wiring between VFD and motor (Non-removable capacitor) If the capacitor in motor is Non-removable, the wiring is as below. The forward and reverse is determined by VW wiring sequence. (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com...
Page 14
VFD-1P-220.240-1HP-7A-DCM (PB) 220VAC Figure 4-13 Wiring between VFD-1P-220.240-1HP-7A-DCM (<=0.75Kw) and motor The forward and reverse is determined by UV wiring sequence. (PB) 220VAC VFD-1P-220.240-1HP-7A-DCM Figure 4-14 Wiring between VFD-1P-220.240-1HP-7A-DCM (<=0.75Kw) and motor Note: After wiring completed, need to set P9.13=2(Thousand's digit)
Page 15
Reverse indicator, indicates that the VFD that the VFD is output reverse phase sequence, when the working in DC motor is connected, the motor is reversed. braking state. (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 15 of 52...
Page 16
Increment of data or function code (increasing the incremental UP key speed when pressed continuously) Decrement of data or function code (increasing decrement DOWN key speed when pressed continuously) (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 16 of 52...
Page 17
2:Serial port control mode selection Running Unit’s digit: 0: Forward 1:Reverse ○ Ten’s digit: 0:REV allowed 1:REV P0.04 direction prohibited setting FWD/REV ○ 0.0~120.0s 0.1s 0.1s P0.05 dead time (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 17 of 52...
Page 18
V/F curve 2: Reduced torque curve 2 (1.7 × P0.22 setting times the power) 3: Reduced torque curve 3 (2.0 times the power) 4: Customized V/F curve (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 18 of 52...
Page 19
P1.12(Pulse min given)~ ○ Pulse max given 0.1K 0.1K P1.14 P1.11(Max input pulse freq.) Corresponding P1.15 ○ freq.to 0.00~Upper limit freq 0.01Hz 50.00Hz pulse max given (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 19 of 52...
Page 31
1: PID reverse action. × P7.32 negative role and Ten’s digit : feedback pressure 0: The feedback pressure is error polarity greater than the actual pressure; (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 31 of 52...
Page 32
0 Restart from the first stage 1 Restart from the freq. of break stage 2 Restart from the running. of break stage LED hundred’s place: parameter save mode selection (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 32 of 52...
Page 34
0: The terminal run command is valid when the power is on 1: The terminal run command is invalid when power is on (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 34 of 52...
Page 35
× ~ PA.05 Motor poles number 2 16 model type Motor stator depends on × ~ PA.06 0.1 5000.0mH 0.1mH inductance model type (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 35 of 52...
Page 36
Output voltage ---- present output voltage Effective value of b-03 Output current 0.1A ---- present output current Present DC bus bar b-04 Bus bar voltage ---- voltage (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 36 of 52...
Page 37
OC1 output terminal state OC2 output terminal state Relay T output terminal state Means invalidity((LED OFF)) Relay R output terminal state Means validity (LED ON) (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 37 of 52...
Page 38
Overvoltage at constant Acc or Dec time is too short Adjust the Acc or Dec time E-06 speed Abnormal change of input Mount input reactor running voltage (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 38 of 52...
Page 39
VFD over current troubleshooting VFD module Output 3-phase fault or ground E-12 Re-wiring protection short Air duct obstruction or fan Clean air duct or replace a damaged new fan (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 39 of 52...
Page 40
R, S, T protection over current Over current when VFD restart press key to reset adjust STOP E-20 fault when and check speed relevant parameters restart (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 40 of 52...
Page 41
If it can’t be reseted or fault occurs again after reset, please check the cause of fault, continuous reset may damage VFD; Ø Reset the VFD after waiting for 5min when overload or overheat protection occurs. (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 41 of 52...
Page 42
PC as host PLC as host PC as host RS232 232-485 232-485 Conversion Conversion RS485 RS485 Single host Single host Multi slaves Multi slaves Fig.8-1 networking of slaves (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 42 of 52...
Page 43
10 characters box(For ASCII) (1-7-2 format, no parity) Start Stop Stop BIT 0 BIT 1 BIT 2 BIT 3 BIT 4 BIT 5 BIT 6 BIT 7 (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 43 of 52...
Page 44
LRC CHK Hi LRC Check code: 8 check code combined with two ASCII code LRC CHK Lo END Hi End character: END Hi = CR(0DH), END Lo = CR(0AH) (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 44 of 52...
Page 45
Asking for information string format Answering information string format “:”---3AH “:”---3AH Header Header “0”---30H “0”---30H Address Address “1”---31H “1”---31H “0”---30H “0”---30H Function code Function code “3”---33H “3”---33H (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 45 of 52...
Page 46
P0.02=50.00HZ to VFD address 01H. : ASCII mode: Asking for information string format Answering information string format Header “:”---3AH Header “:”---3AH “0”---30H “0”---30H Address Address “1”---31H “1”---31H (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 46 of 52...
Page 47
This command is used to test the communication between main control equipm- ent and VFD. VFD receives and sends back the message to the main control equipment. (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 47 of 52...
Page 48
Asking for information string format Answering information string format Address Address Function code Function code content content CRC CHECK Low CRC CHECK Low CRC CHECK High CRC CHECK High (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 48 of 52...
Page 49
Commands 2000H to VFD 0006H REV JOG : (06H) 0007H DEC and STOP : 0008H STOP : 0009H JOG STOP : 000AH RESET : 2001H Freq. setting (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 49 of 52...
Page 50
2109H Read VI analog input 210AH Read CI analog input Read software version 210BH 210CH Read VFD terminal status Read set pressure 210DH 210EH Read feedback pressure (877) 348-9680 Larson Electronics, LLC Phone: Fax: (903) 498-3364 www.larsonelectronics.com 50 of 52...
Page 51
(i.e. excessive dust build-up). Clean with a non-abrasive cloth if needed. 4. Do not operate if the lens is cracked or damaged. All fasteners should be properly seated. (877) 348-9680 Larson Electronics, LLC Larson Electronics, LLC P Phone: Fax: (903) 498-3364 www.larsonelectronics.com...
Page 52
REPLACEMENT PARTS The VFD-1P-220.240-1HP-7A-DCM is designed to provide years of reliable performance. Should the need for replacement parts arise, please contact Larson Electronics. THESE INSTRUCTIONS MAY NOT COVER ALL DETAILS OR VARIATIONS OF THIS PRODUCT FOR YOUR EQUIPMENT OR INSTALLATION REQUIREMENTS.
Need help?
Do you have a question about the VFD-1P-220.240-1HP-7A-DCM and is the answer not in the manual?
Questions and answers
I do not see a speed regulation potentiometer interface on the schematic, does this drive allow external speed control?