Solar - Viessmann VITODENS 200-W B2HA 150 Service Instructions Manual

Hide thumbs Also See for VITODENS 200-W B2HA 150:
Table of Contents

Advertisement

Coding 2

Solar

Select "Solar"
Note: The solar group is only displayed if a solar control module, type SM1, is connected.
Coding
Coding in the factory setting
00:8
01:4
02:0
03:10
04:4
05:10
06:75
07:0
08:60
58
The solar circuit pump starts
when the collector temperature
exceeds the actual DHW tank
temperature by 8 K.
The solar circuit pump is switched
off when the differential between
the collector temperature and the
actual DHW tank temperature is
less than 4 K.
Solar circuit pump (stepped)
is not speed-controlled
The temperature differential
between the collector
temperature and actual DHW
tank temperature is regulated
to 10 K.
Controller amplification of the
speed control 4%/K.
Minimum speed of the solar
circuit pump 10% of the
maximum speed.
Maximum speed of the solar
circuit pump 75% of the
maximum possible speed.
Interval function of the solar
circuit pump switched off.
The solar circuit pump is
switched off when the
actual DHW tank temperature
reaches 140°F (60°C)
(maximum DHW tank
temperature).
Vitodens 200-W B2HA 112, 150, 399, 530 Service
Possible change
00:2
The differential between
to
the actual DHW tank temperature
00:30
and the start point for the solar
circuit pump can be adjusted from
2 to 30 K.
01:1
The differential between the
to
actual DHW tank temperature and
01:29
the stop point for the solar circuit
pump can be adjusted from 1 to
29 K.
02:1
Solar circuit pump is speed-
controlled with wave packet
control.
02:2
Solar circuit pump is speed-
controlled with PWM control.
03:5
The differential temperature
to
control between collector
03:20
temperature and actual DHW tank
temperature can be adjusted from
5 to 20 K.
04:1
Controller amplification adjustable
to
from 1 to 10%/K.
04:10
05:2
Minimum speed of the solar
to
circuit pump is adjustable from
05:100
2 to 100%.
06:1
Maximum speed of the solar
to
circuit pump is adjustable from 1
06:100
to 100%.
07:1
Interval function of the solar
circuit pump switched on. To
capture the collector temperature
more accurately, the solar circuit
pump starts for short cycles.
08:10
The maximum DHW tank
to
temperature can be adjusted
08:90
from 50 to 194°F (10 to 90°C).

Advertisement

Table of Contents
loading

Table of Contents