INCOMM L510 LAMP CONTROLLER USER GUIDE
Set the RF Channel:
a. Use the UP/DOWN arrow buttons to select RF.
b. Press MODE
c. Use the UP/DOWN arrow buttons to select the RF Channel value.
d. Press FAN to store the value in memory.
e. Press °F|°C to exit service mode.
3.
With the required Room ID, PAN ID, and RF Channel entered into the thermostat, now Bind the L510. There are two options:
• Teach Address Bind – Set a defined Address into the L510 in addition to the Room ID, PAN ID, and RF Channel.
a. Use the UP/DOWN arrow buttons in SERVICE MODE to select Adr.
b. Press MODE. The display changes to show Adr and an address value. Use the UP/DOWN arrow buttons to change the
displayed value to the desired address.
c. Press FAN to place the thermostat into reverse bind mode. The L510 uses a reverse bind.
The thermostat display will show bnd, indicating it is waiting to see a reverse bind command from the L510. On the
L510, press its Bind/Service button to make the L510 send a Bind Request. The thermostat will send a Bind Offer to the
L510 containing the defined values when it sees this message. If the L510 received the Bind Offer, it would RESET and,
upon startup, start using the new, designated Address and send 3 Sound buzzer messages to make the thermostat beep
as an indication that the L510 was bound.
• Press °F|°C three times to exit service mode.
• Teach I/O Bind - Activate a stored I/O map configuration in the L510 and set the Room ID, PAN ID, and RF Channel.
a. Use the UP/DOWN arrow buttons in SERVICE MODE to select Io.
b. Press MODE. The display changes to show Io and an I/O Map value. Use the UP/DOWN arrow buttons to change the
displayed value to the desired I/O map.
c. Press FAN to place the thermostat into reverse bind mode. The L510 uses a reverse bind.