Honeywell INCOMM L510 User Manual page 10

Lamp controller
Table of Contents

Advertisement

INCOMM L510 LAMP CONTROLLER USER GUIDE
Set the RF Channel:
a. Use the UP/DOWN arrow buttons to select rF.
b. Press DISPLAY
c. Use the UP/DOWN arrow buttons to select the RF Channel value.
d. Press DISPLAY to store the value in memory.
e. Press °F|°C to exit service mode.
3. With the required Room ID, PAN ID, and RF Channel entered into the thermostat, now Bind the L510. There are two options:
• Teach Address Bind - This sets the defined Address into the L510 in addition to the Room ID, PAN ID, and RF Channel.
a. In SERVICE MODE, use the UP/DOWN arrow buttons to select Adr.
b. Press DISPLAY. The display changes to show V and a value. Use the UP/DOWN arrow buttons to change the displayed
value to the desired address.
c. Initiate the Reverse Bind:
—"For the E528/E527, press OFF/AUTO to place the thermostat into reverse bind mode. The L510 uses a reverse bind.
The E528/E527 will display bnd, indicating it is waiting to see a reverse bind command from the L510.
—For the E529, do nothing. Leave the E529 displaying the desired Address.
On the L510, press its Bind/Service button to make the L510 send a Bind Request. The thermostat will send a Bind
Offer to the L510 containing the defined values when it sees this message. If the L510 received the Bind Offer, it will
RESET and, upon startup, begin using the defined Address and send 3 Sound buzzer messages to make the
thermostat beep as an indication that the L510 was bound.
—Press °F|°C three times to exit service mode.
• Teach Address Bind - Activate a stored I/O map configuration in the L510 and set the Room ID, PAN ID, and RF Channel.
a. In SERVICE MODE, use the UP/DOWN arrow buttons to select Io.
b. Press DISPLAY. The display changes to show V and a value. Use the UP/DOWN arrow buttons to change the displayed
value to the desired I/O map.
c. Initiate the Reverse Bind:
—For the E528/E527, press OFF/AUTO to place the thermostat into reverse bind mode. The L510 uses a reverse bind. The
E528/E527 will display bnd, indicating it is waiting to see a reverse bind command from the L510..
—For the E529, do nothing. Leave the E529 displaying the desired I/O Map.
On the L510, press its Bind/Service button to make the L510 send a Bind Request. The thermostat will send a Bind
Offer to the L510 containing the defined values when it sees this message. If the L510 received the Bind Offer, it will
RESET and, upon startup, begin using the new I/O Map configuration and send 3 Sound buzzer messages to make
the thermostat beep as an indication that the L510 was bound.
—Press °F|°C three times to exit service mode.
4. Test the functionality of the L510.
31-00593-01
10
v1.5 October 26, 2022

Advertisement

Table of Contents
loading

Table of Contents