6� Operation/configuration
Configuring sensor via USB
• Provide power supply via IP module.
• Remove micro USB cover. (Fig. 6.1)
• Connect sensor to a PC or laptop using a micro USB cable. (Fig. 6.1)
The PC will now show a new network adapter.
• If necessary, install the the RNDIS driver on your laptop.
• Configure network adapter with IPv4 address 10.88.0.1.
• Start web browser.
• Open the configuration interface via the USB standard IP address: 10.88.0.2.
– The standard password for the USB interface (web server via USB) is:
adm123
– The password for opening the image is: steinel
Note: the USB interface is only available for the first 30 minutes of switching the
sensor ON.
Setting the IP interface
– Set up LAN access to the sensor. DHCP is factory-activated.
• Check which IP address the sensor has been given. Use this to open the
web interface.
– If no DHCP server is available, fallback IP address 192.168.1.200 will be
used (subnet is 192.168.1.0/24). In this case, the computer must be set to
the same subnet (192.168.1.0/24).
• Start web browser. Open configuration interface via the standard IP address.
A static IP or a DHCP client can be set up via
the web interface.
– Instead of using the IP address, the sensor can also be accessed via the
host name. The standard host name is: "steinel_" + the last 6 characters of
the MAC address + ".local".
Example:
MAC address is CC:BD:35:12:34:56,
the host name is: steinel_123456.local.
– The standard passwords for the IP interface are:
– Admin password: adm123
– User password: updwd123
– 37 –