Safety Information - Testboy TV 440N Instruction Manual

Earth resistance tester
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 12
 
GB 
 
 
 
INTRODUCTION 
This tester can measure grounding resistance and AC voltage up to 200V. 2mA current test signal permits 
grounding resistance tester without tripping current breakers in the circuit under fest. lt can be used in the 
grounding resistance measurements of Power System, electrical device, lightning protection device, etc. lt is 
easy to use and has a high precision. 
 
SAFETY INFORMATION 
This fester has been designed according to IEC‐61010 concerning electronic measuring instruments with a 
measurement category (CAT III 200V). 
Warning 
To avoid possible electric shock or personal injury, follow these guidelines: 
• 
Do not use the tester if it is damaged. Before you use the fester, inspect the Case. Pay particular 
attention to the insulation surrounding the connectors. 
• 
Inspect the test leads for damaged insulation or exposed metal. Check the fest leads or continuity. 
Replace damaged fest leads before you use the tester. 
• 
Do not use the tester if it operates abnormally. Protection 
may be impaired. When in doubt, have the tester serviced. 
• 
Do not operate the tester around explosive gas, vapor, or dust. 
• 
Do not apply more than the rated voltage, as marked on the fester, between terminals or between 
any terminal and earth ground. 
• 
Before use, verify the testers operation by measuring a known voltage. 
• 
When servicing the fester, use only specified replacement parts. 
• 
Use caution when working above 30V ac RMS, 42V peak, or 60V dc. Such voltages pose a shock 
hazard. 
• 
When using the probes, keep your fingers behind the finger guards on the probes. When using the 
Clips, don't touch metal or conductor with finger or skin for safely. 
• 
Remove the fest leads from the tester before you open the battery door or the case. 
• 
Do not operate the tester with the battery door or portions of the case removed or loosened. 
• 
To avoid false readings, which could lead to possible electric shock or personal injury, replace the 
batteries as soon as the low battery indicator appears or when the display is blank. 
• 
Don't use hand or skin to touch any earth electrode which may be live or high power. Don't use hand 
or skin to touch any auxiliary earth bar while testing. 
Remaining endangerment: 
When an input terminal is connected to dangerous live potential it is to be noted that this potential at 
all other terminals can occur! 
• 
If the tester is used in a manner not specified by the manufacturer, the protection provided by the 
fester will be impaired. 
• 
CAT III is for measurements performed in the building Installation, examples in measurements in 
distribution boards, circuitbreakers, wiring, including gables, bus‐bare, junction boxes, switches, 
socket outlets in the fixed Installation, and equipment for industrial use and some other equipment, 
for example, stationary motors with permanent connection to the fixed installation. Don't use the 
equipment tor measurement within Measurement Categories IV. 
 
Caution 
To avoid possible damage to the tester or to the equipment under fest, follow these guidelines: 
• 
Use the proper terminals, function, and range for your measurements. 
• 
Before turning on the tester for measuring, make sure that the plugs of the fest leads have been well 
inserted to the specified sockets. 
• 
Before turning the function/range switch to change functions, disconnect test leads from the circuit 
(or object) under fest. 
• 
Remove fest leads from the tester before opening the battery door or case. 
• 
Don't use the tester in damp weather. 
  
 
 
 
 
Instruction Manual 
11

Advertisement

Table of Contents
loading

Table of Contents