Explanations:
d0 Parameter Disable:
Enter value (d0) to disable any Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.4-
06), M4 (Pr.4-07) or M5 (Pr.4-08).
NOTE
The purpose of this function is to provide isolation for unused Multi-Function Input Terminals. Any
unused terminals should be programmed to d0 to insure they have no effect on drive operation.
d1 Two wire operation: Restricted to Pr.4-04 and external terminals M0, M1.
d2 Two wire operation: Restrict to Pr. 4-04 and external terminals M0, M1.
NOTE
Multi-function Input Terminal M0 does not have its own parameter designation. M0 must be used in
conjunction with M1 to operate two and three wire control.
d3 Three Wire Control: Restricted to Pr.4-04 control terminals M0, M1, M2.
STOP
Revision August 2008, SE09, SW V2.61
FWD/STOP
M0 "Open": Stop, "Close": FWD Run
REV/STOP
M1 "Open": Stop, "Close":REV Run
GND
M0 "Open": Stop, "Close": Run
RUN/STOP
M1 "Open": FWD, "Close":REV
REV/FWD
GND
RUN
M0 Run command, Runs when "close"
M2 Stop command, stops when "Open"
M1 REV/FWD Run selection
"Open": FWD Run
REV/FWD
"Close": REV Run
GND
Chapter 5 Parameters|VFD-S Series