Display
(Pr.0-04=d1)
Counter Trigger Signal
Multi-function Input Terminal
Preliminary Counter Value Attained Output
(Pr. 3-04=d3)
(Pr. 3-05 to Pr. 3-06=d15)
Terminal Count Value Attained Output
(Pr.3-03=d5)
(Pr.3-05 to Pr.3-06=d14)
3-05
Multi-function Output Terminal 1 (Photocoupler output)
3-06
Multi-function Output Terminal 2 (relay output)
Settings d0 to d18
Setting
d0
No Function
d1
AC Drive Operational
Master Frequency Attained
d2
d3
Zero Speed
d4
Over Torque Detection
d5
Base-Block (B.B.) Indication the output will be activated when the output of the AC
d6
Low-Voltage Indication
d7
Operation Mode Indication
d8
Fault Indication
d9
Desired Frequency Attained the output will be activated when the desired frequency
Revision August 2008, SE09, SW V2.61
TRG
Function
the output terminal will be activated when the drive is
running.
the output will be activated when the AC drive attains
Maximum Output Frequency.
the output will be activated when Command Frequency
is lower than the Minimum Output Frequency.
the output will be activated as long as the over-torque is
detected. Pr.6-04 determines the Over-Torque detection
level.
drive is shut off by external Baseblock.
the output will be activated when low voltage is detected.
the output will be activated when the operation of the AC
drive is controlled by External Control Terminals.
the output will be activated when faults occur (oc, ov,
oH, oL, oL1, EF, cF3, HPF, ocA, ocd, ocn, GF).
(Pr.3-02)is attained.
Chapter 5 Parameters|VFD-S Series
2ms
The width of trigger signal
should not be less than
2ms(<250 Hz)
Factory Setting: d1
Factory Setting: d8
Description
2ms
5-33