Delta Electronics VFD S 115V Series User Manual page 65

Compact low-cost easy-to-use general-purpose ac motor drives
Table of Contents

Advertisement

Chapter 5 Parameters|VFD-S Series
Pr.
6-04
Over-Torque Detection Level
6-05
Over-Torque Detection Time
Electronic Thermal Overload Relay
6-06
Selection
Electronic Thermal
6-07
Characteristic
6-08
Present Fault Record
6-09
Second Most Recent Fault Record
6-10
Third Most Recent Fault Record
5-8
Explanation
Settings
d4: Enabled during running. After
the over-torque is detected, stop
running.
d30 to d200%
d0.1 to d10.0 Sec
d0 to d2
d30 to d600 Sec
d0: No fault
d1: Over current (oc)
d2: Over voltage (ov)
d3: Over heat (oH)
d4: Over load (oL)
d5: Over load (oL1)
d6: External fault (EF)
d7: Reserved
d8: Reserved
d9: Excess current during
acceleration (ocA)
d10: Excess current during
deceleration (ocd)
d11: Excess current during steady
state (ocn)
d12: Ground fault (GF)
d13: Reserved
d14: Low voltage (Lv)
d15: CPU failure 1 (cF1)
d16: CPU failure 2 (cF2)
d17: Base block (b.b.)
d18: Overload (oL2)
d19: Auto acceleration/deceleration
failure (cFA)
d20: Software protection enable
(codE)
d21: Reserved
d22: CPU failure (cF3.1)
d23: CPU failure (cF3.2)
d24: CPU failure (cF3.3)
d25: CPU failure (cF3.4)
d26: CPU failure (cF3.5)
d27: CPU failure (cF3.6)
d28: CPU failure (cF3.7)
d29: Hardware protection failure
(HPF.1)
d30: Hardware protection failure
(HPF.2)
d31: Hardware protection failure
(HPF.3)
d32: Communication time-out
(CE10)
d33: Reserved
d34: Software error (SErr)
Revision August 2008, SE09, SW V2.61
Factory
NOTE
Setting
d150
d0.1
d2
d60
d0

Advertisement