YASKAWA GA80U4720ABM Manual page 348

Table of Contents

Advertisement

7.6 Parameter Setting Errors
Code
Name
Code
Name
oPE05
Run Cmd/Freq Ref Source Sel Err
348
Causes
These commands are set in Digital Inputs (H1-xx, F3-
10 to F3-25, and H7-01 to H7-04) at the same time:
• Setting values 61 [Speed Search from Fmax] and
62 [Speed Search from Fref]
• Setting values 65, 66, 7A, 7B [KEB Ride-Thru 1 or
2 Activate] and 68 [High Slip Braking (HSB)
Activate]
• Setting values 16 [Motor 2 Selection] and 1A
[Accel/Decel Time Selection 2]
• Setting values 65, 66 [KEB Ride-Thru 1 Activate]
and 7A, 7B [KEB Ride-Thru 2 Activate]
• Setting values 40, 41 [Forward RUN (2-Wire),
Reverse RUN (2-Wire)] and 42, 43 [Run
Command (2-Wire Sequence 2), FWD/REV (2-
Wire Sequence 2)]
• Setting values 60 [DC Injection Braking
Command] and 6A [Drive Enable]
• Setting values 16 [Motor 2 Selection] and 75, 76
[Up 2 Command, Down 2 Command]
Settings for N.C. and N.O. input [H1-xx] for these
functions were selected at the same time:
• Setting value 15 [Fast Stop (N.O.)]
• Setting value 17 [Fast Stop (N.C.)]
These settings were entered while H1-xx = 2
[External Reference 1/2 Selection]:
• b1-15 = 4 [Frequency Reference Selection 2 =
Pulse Train Input]
• H6-01 ≠ 0 [Terminal RP Pulse Train Function ≠
Frequency Reference]
These settings were entered while H1-xx = 2
[External Reference 1/2 Selection]:
• b1-15 = 3 [Option PCB] or b1-16 = 3 [Run
Command Selection 2 = Option PCB]
• No option card is connected to the drive.
These settings were entered while H1-xx = 2
[External Reference 1/2 Selection]:
• b1-15 = 1 [Analog Input]
• H3-02 ≠ 0 [Terminal A1 Function Selection ≠
Frequency Reference] or H3-10 ≠ 0 [Terminal A2
Function Selection ≠ Frequency Reference]
These parameters are set at the same time:
• H1-xx ≠ 6A [Drive Enable]
• H2-xx = 38 [Drive Enabled]
These parameters are set at the same time:
• H6-01 ≠ 3 [PG Speed Feedback (V/F Control)]
• H1-xx = 7E [Reverse Rotation Identifier]
These parameters are set at the same time:
• H1-xx = 75/76 [Up 2 /Down 2 Command]
• H3-01, H3-05, H3-09 = 1 [Terminal A1, A2, A3
Signal Level Select = -10 to +10V (Bipolar
Reference)]
These parameters are set at the same time:
• H1-xx = 62 [Speed Search from Fref]
• H5-22 = 1 [Speed Search from MODBUS =
Enabled]
These settings do not agree:
• A PG-RT3 option is connected to the drive.
• H1-xx = 16 [Motor 2 Selection] is set.
Causes
The setting to assign the Run command or frequency
reference to an option card or the pulse train input is
incorrect.
b1-01 = 3 [Frequency Reference Selection 1 =
Option PCB] is set, but there is no option card
connected to the drive.
b1-02 = 3 [Run Command Selection 1 = Option
PCB] is set, but there is no option card connected to
the drive.
Possible Solutions
Remove the function settings that are not in use.
Remove one of the function settings.
Set H6-01 = 0.
Connect an input option card to the drive.
Set H3-02 = 0 or H3-10 = 0.
Correct the parameter settings.
Correct the parameter settings.
Remove one of the function settings.
Remove one of the function settings.
Correct the parameter settings.
Note:
The Motor Switch function is not available with the PG-RT3
option.
Possible Solutions
Correct the parameter settings.
Connect an option card to the drive.