8.5.5 Other settings

Pr. 84
"rated motor speed"
The rated speed of the motor used with the drive unit is displayed. This
parameter is for read-only and its value cannot be changed.
Pr. 244
"cooling fan operation selection"
When the drive unit has a built-in cooling fan, you can select the operation of the
cooling fan.
Setting
0
While the drive unit power is on, the cooling fan keeps running.
While the motor is operating, the cooling fan keeps running. While the motor is
1
at a stop, the cooling fan is stopped according to the temperature of the drive
unit.
If the cooling fan stops due to a failure, the "FN" alarm indication
appears on the parameter unit.
That the cooling fan has stopped due to a failure can be exported as
MEMO
an alarm signal.
When Pr. 244 = 1, the alarm function is activated if the fan starts
running during the fan "OFF" command.
Operation
Refer to: Chapter 6, 6.1.2 Alarm function
activated
Refer to: 8.7.2 Selection of the control
circuit output terminal functions