9. Maintenance

Service Manual

9.1 Error Code List

Display Method
Malfunction
of Indoor Unit
Name
(Error Code)
High pressure
protection of
system
Antifreezing
protection for
evaporator
System block
or refrigerant
leakage
High discharge
temperature
protection of
compressor
Overcurrent
protection
Communi-
cation
Malfunction
High
temperature
resistant
protection
EEPROM
malfunction
Limit/decrease
frequency due
to high
temperature of
module
Malfunction
protection of
jumper cap
Refrigerant
insufficient
protection, cut
off protection of
refrigerant
Indoor ambient
temperature
sensor is
open/short
circuited
Indoor
evaporator
temperature
sensor is
open/short
circuited
Installation and Maintenance
A/C Status
During cooling and drying operation,
except indoor fan operates, all loads
E1
stop operation.
During heating operation, the complete
unit stops.
E2
The Dual-8 Code Display will show
E3
E3 until the low pressure switch stop
operation.
During cooling and drying operation,
compressor and outdoor fan stop while
E4
indoor fan operates. During heating
operation, all loads stop.
During cooling and drying operation,
compressor and outdoor fan stop while
E5
indoor fan operates. During heating
operation, all loads stop.
During cooling operation, compressor
stops while indoor fan motor operates.
E6
During heating operation, the complete
unit stops.
During cooling operation: compressor
will stop while indoor fan will operate.
E8
During heating operation, the complete
unit stops.
During cooling and drying operation,
compressor will stop while indoor fan will
EE
operate;
During heating operation, the complete
unit will stop
All loads operate normally, while
EU
operation frequency for compressor is
decreased
Wireless remote receiver and button are
C5
effective, but can not dispose the related
command
Cool/Dry:compressor and outdoor fan
F0
will stop while indoor fan will operate;
Heat: all loads stops operation.
During cooling and drying operation,
indoor unit operates while other loads
F1
will stop; during heating operation, the
complete unit will stop operation.
AC stops operation once reaches the
setting temperature. Cooling, drying:
F2
internal fan motor stops operation while
other loads stop operation; heating: AC
stop operation
Possible Causes(For specific maintenance
method, please refer to the following procedure of
troubleshooting)
Possible reasons:
1. Refrigerant was superabundant;
2. Poor heat exchange (including filth blockage of heat
exchanger and bad radiating environment ); Ambient
temperature is too high.
Not the error code. It's the status code for the operation.
1.Low-pressure protection
2.Low-pressure protection of system
3.Low-pressure protection of compressor
Please refer to the malfunction analysis (discharge
protection, overload).
1. Supply voltage is unstable;
2. Supply voltage is too low and load is too high;
3. Evaporator is dirty.
Refer to the corresponding malfunction analysis.
Refer to the malfunction analysis (overload, high temperature
resistant).
Replace outdoor control panel AP1
Discharging after the complete unit is de-energized for
20mins, check whether the thermal grease on IPM Module
of outdoor control panel AP1 is sufficient and whether the
radiator is inserted tightly.
If its no use, please replace control panel AP1.
1. No jumper cap insert on mainboard.
2. Incorrect insert of jumper cap.
3. Jumper cap damaged.
4. Abnormal detecting circuit of mainboard.
1. Is system cooling under high humidity environment, thus
temperature difference of heat transfer is small;
2. Check whether the big valve and small valve of outdoor
unit are opened completely;
3. Is the temperature sensor of evaporator of indoor unit
loose?
4. Is the temperature sensor of condenser of outdoor unit
loose?
5. Is the capillary or the electronic expansion valve blocked?
6. Is refrigerant leaking?
1. Loosening or bad contact of indoor ambient temp. sensor
and mainboard terminal.
2. Components in mainboard fell down leads short circuit.
3. Indoor ambient temp. sensor damaged.(check with sensor
resistance value chart)
4. Mainboard damaged.
1. Loosening or bad contact of Indoor evaporator temp.
sensor and mainboard terminal.
2. Components on the mainboard fall down leads short
circuit.
3. Indoor evaporator temp. sensor damaged.(check temp.
sensor value chart for testing)
4. Mainboard damaged.
75