4. Locate the RTRM (J6). Connect two (2) wires to
terminals J6-1 and 2.
5. Connect the sensor (OAS) using two wire nuts to the
two (2) field supplied wires that were connected to
terminals 1 and 2 on J6.
Unit Economizer Control (ECA)
Troubleshooting ReliaTel Control
Verify Economizer Status by Economizer Actuator (ECA)
LED indicator:
OFF: No Power or Failure
ON: Normal, OK to Economize
Slow Flash: Normal, Not OK to Economize
Fast Flash - 1/4 Second On / 2 Seconds Off:
– Error Code: Communications Failure
Pulse Flash: 1/30 Second On / 1/4 Second Off: (2
Seconds between pulse sequences)
Error Code:
1 Flash: Actuator Fault
2 Flashes: CO
Sensor
2
3 Flashes: RA Humidity Sensor
4 Flashes: RA Temp Sensor
5 Flashes: OA Quality Sensor
6 Flashes: OA Humidity Sensor
7 Flashes: OA Temp Sensor
8 Flashes: MA Temp Sensor
9 Flashes: RAM Fault
10 Flashes: ROM Fault
11 Flashes: EEPROM Fault
RT-SVX25M-EN
Troubleshooting
47