Gree GMV-Y96WM/A-F(U) Owner's Manual page 53

Commercial air conditioners photovoltaic multi vrf
Table of Contents

Advertisement

Photovoltaic Multi VRF
——
Debugging code
progress
Code
db
Step 18: if there's no error during operation for about 40min, system will automatically confirm
that debugging is finished and then stop. System resumes standby condition and displays as below:
——
Debugging code
progress
Code
17_Debugging
01-04
finished
Step 19: after debugging is finished, some functions can be set up according to project's actual
needs. For specific details, please refer to System Functions Setup. If no special requirements, skip
this step.
Step 20: deliver the product to user and inform user about usage precautions.
5.2.3 Appendix: judgment reference of normal operational parameters
Reference of Debug Parameters of
No.
Debug item
1
2
3
4
System
ODU
parameters
5
6
Progress code
LED1
LED2
Display
Display
code
status
status
Light
16
Light
Progress code
LED1
LED2
Display
Display
code
status
status
Light
OF
Light
Parameter name
Outdoor ambient temp
Discharge tube temp of
inverter compressor 1
Casing top temp of
inverter compressor 1
Discharge tube temp of
inverter compressor 2
Casing top temp of
inverter compressor 2
Defrost temp 1
Status code
LED3
Display
Code
status
System detects error in indoor pipeline.
XXXX is the project no. of the faulted
IDU. 3s later, error code U8 is
XXXX
Light
displayed. For example, IDU no. 100
/U8
has U8 error, then LED3 displays like
this: 01 (2s later) 00 (2s later) U8, and
repeat again.
Status code
LED3
Display
Code
status
Debugging is finished. System is on
standby condition. LED1 displays
OF
Light
module address. LED2 and LED3
display "OF".
photovoltaic multi VRF
Unit
º C(° F)
● When system compressor starts up, temp of
º C(° F)
discharge tube or casing top in cooling mode is
within 70~95º C (158~203° F), and at least 10
º C(° F)
º C(50° F) higher than system high pressure
saturation temp; Temp in heating mode is within
65~80º C(149~176° F), and at least 10º C(50° F)
º C(° F)
higher than system high pressure saturation temp.
● When inverter compressor starts but inverter
compressor 2 stops, the discharge tube temperature
º C(° F)
of inverter compressor 2 is almost the same with
ambient temp.
● In cooling mode, defrost temp1 is 5~11ºC
(41~51.8° F) lower than system high pressure value;
º C(° F)
● In heating mode, defrost temp1 is about 2ºC
(35.6° F) different from system low pressure value.
49