than 1m(39-3/8in.), please refer to the following table for charging amount of refrigerant. (Liquid
pipe prevails)
How much additional refrigerant should be charged
Total refrigerant charging amount R= Pipeline charging amount A + ∑charging amount B of
every module
(1) Pipeline charging amount
Added refrigerant quantity A for piping = ∑Liquid pipe length × Added refrigerant quantity
for each meter(in.) of liquid pipe
28.6(1-1/8)
kg/m
0.680
OZ/in.
0.61
(2) ∑Refrigerant charging amount B of every module
Refrigerant charging amount B of every module kg(Pounds)
IDU/ODU rated capacity
collocation ratio C
50%≤C≤90%
90%<C≤105%
105%<C≤135%
IDU/ODU rated capacity collocation ratio C = Sum of rated cooling capacity of indoor unit / Sum of rated
cooling capacity of outdoor unit
If all of the indoor units are fresh air indoor units, the quantity of refrigerant added to each module is 0kg.
If outdoor air processor is connected with normal VRF indoor unit, adopt the perfusion method for normal
indoor unit for perfusion.
For example1:
The OUD is composed of 1 module: 96kBtu/h. The IDUs are made up of 5sets of 18
kBtu/h.
IDU/ODU rated capacity collocation ratio C= 18×5/96=93.75%. The quantity of included
IDUs is more than 4 sets. Please refer to the above table.
Refrigerant charging amount B for 96 kBtu/h module is 2.0kg(4.4pounds).
Suppose the Pipeline charging amount A=Σ Liquid pipe length × refrigerant charging
amount of every 1m (or 1in.) liquid pipe=5kg (11.0 pounds)
Total refrigerant charging amount R=5+2=7kg (11.0+4.4=15.4pounds).
For example 2:
Outdoor unit is a 96kBtu/h module and the indoor unit is a 96kBtu/h fresh air unit. The
quantity (B) of refrigerant added to this module is 0kg (0pounds).
Diameter of liquid pipe mm(in.)
25.4(1)
22.2(7/8)
19.05(3/4)
0.520
0.350
0.47
0.31
Quantity of included IDUs(N)
15.9(5/8)
0.250
0.170
0.22
0.15
N<4
N≥4
N<4
8>N≥4
N≥8
N<4
8>N≥4
N≥8
23
12.7(1/2)
9.52(3/8)
0.110
0.054
0.10
0.05
Rated Capacity(1000Btu/h)
96
0
0.5(1.1)
1(2.2)
2(4.4)
3.5(7.7)
2(4.4)
3.5(7.7)
4.5(9.9)
6.35(1/4)
0.022
0.02