Gree GMV-Y96WM/A-F(U) Owner's Manual page 37

Commercial air conditioners photovoltaic multi vrf
Table of Contents

Advertisement

Photovoltaic Multi VRF
When two wired controllers control multiple IDUs, the wired controller can be connected to
any one IDU, provided that the connected IDU is of the same series. Meanwhile, one and only
one of the wired controllers must be set as a slave controller. At most 16 IDUs can be controlled
by wired controllers and the connected IDUs shall be within a same IDU network.
No matter when unit is turned on or off, slave controller can be set.
How to set a slave controller: hold "function" button on the designated controller for 5s, and
temperature zone displays C00. Continue holding "function" button for 5s and setting screen of
controller parameter will come out. Default temperature zone displays P00.
Press
button or
switch to setup of parameter values. Then the parameter value will blink. Press
button to select code 02. And then press "confirm/cancel" to finish setting.
Press "confirm/cancel" to return to the previous display until you exit from the setup of
parameter values.
Below are user's parameter settings:
Parameter
Parameter
code
name
Set up
address for
P13
wired
controller
button to select parameter code P13. Press "mode" button to
Default
Parameter scope
value
01: master wired
controller
02: slave wired
controller
33
When 2 wired controllers control one or more
IDUs, they shall have different addresses.
01
Slave wired controller (02) can't set up units'
parameters except its own address.
button or
Remark