Power supply for fire detection and fire alarm systems, smoke and heat control systems, and other fire protection systems
Hide thumbs Also See for ZSP135-DR-2A-1:

Advertisement

Quick Links

User manual ZSP135-DR
MERAWEX Sp. z o.o
44-122 Gliwice
ul. Toruńska 8, Poland
tel. +48 32 23 99 400
fax +4832 23 99 409
e-mail:
merawex@merawex.com.pl
http://www.merawex.com.pl
Power supply for fire detection and fire alarm systems, smoke and heat control
ZSP135-DR-2A-1, ZSP135-DR-3A-1, ZSP135-DR-3A-2,
ZSP135-DR-5A-1, ZSP135-DR-5A-2, ZSP135-DR-5A-3,
ZSP135-DR-7A-1, ZSP135-DR-7A-2, ZSP135-DR-7A-3
conforming to the standard EN 54-4:1997/A2:2006 and EN 12101-10:2005,
guidelines of VdS 2541:1996-12, 2882:2004-11, 2824:2004-03, 2593:2002-09
as well as to the Ordinance of the Polish Minister of Interior and Administration of
20.6.2007 (Dz.U. Nr 143, poz. 1002, amended on 27.04.2010),
1.
TECHNICAL DESCRIPTION
2.
SET-UP
3.
SWITCHING ON FOR THE FIRST TIME
4.
OPERATION
5.
REPAIRS
6.
REMARKS ON THE SELECTION OF THE TYPE OF THE POWER SUPPLY
7.
ADDITIONAL INFORMATION
No. in the documentation system: 0404.00.95-02.2
No. of the Polish original: 0404.00.95-01.5, 17.01.2012
No. of documentation 0404.00.95-02.2
USER MANUAL
systems, and other fire protection systems
in a casing of ingress protection IP44
Certificate of conformity CNBOP No. 1438/CPD/0163
Certificate of approval CNBOP No. 0583/2009
Certificate of approval VdS No. G 511007
17.01.2012
Page 1/12
2
4
6
7
9
11
11

Advertisement

loading
Need help?

Need help?

Do you have a question about the ZSP135-DR-2A-1 and is the answer not in the manual?

Questions and answers

Summary of Contents for MERAWEX ZSP135-DR-2A-1

  • Page 1 User manual ZSP135-DR No. of documentation 0404.00.95-02.2 Page 1/12 MERAWEX Sp. z o.o 44-122 Gliwice ul. Toruńska 8, Poland tel. +48 32 23 99 400 fax +4832 23 99 409 e-mail: merawex@merawex.com.pl http://www.merawex.com.pl USER MANUAL Power supply for fire detection and fire alarm systems, smoke and heat control...
  • Page 2: Technical Description

    (see the section 4.3) Nominal output Maximal output Battery Type of the Type current current capacity Imax a Imax b ZSP135-DR-2A-1 1.0A 18Ah ZSP135-DR-3A-1 2.0A 18Ah ZSP135-DR-3A-2 1.5A 28Ah ZSP135-DR-5A-1 4.0A...
  • Page 3 User manual ZSP135-DR No. of documentation 0404.00.95-02.2 Page 3/12 Depending on the battery bank capacity the power supplies are assembled into three types of wall boxes. Typ of the box Dimensions 390 x 350 x 90 390 x 350 x 140 450 x 350 x 180 1.2.
  • Page 4 No. of documentation 0404.00.95-02.2 Page 4/12 ZSP135-DR MERAWEX Exemplary outer layout of the power supply (ZSP135-DR-5A-1) and location of the mounting holes. The detailed technical description of the power supply ZSP135-DR could be found in the technical documentation, no. of the document 0404.00.91-01.4 section 2.
  • Page 5 User manual ZSP135-DR No. of documentation 0404.00.95-02.2 Page 5/12 The installation cables can enter the box from the top through three cable transits PG-11 and one PG-9 (dedicated for remote indication cables). All connections should be carried out according to the diagram inside the box (on the door).
  • Page 6 User manual ZSP135-DR No. of documentation 0404.00.95-02.2 Page 6/12 Batteries are delivered in separate transport packages. They should be connected with wires delivered by the manufacturer. Before the connection the batteries have to be put on the bottom of the box.
  • Page 7 User manual ZSP135-DR No. of documentation 0404.00.95-02.2 Page 7/12 4. Operation 4.1. Introduction Output voltages and state indication thresholds are factory preset. After having set up the power supplies require ongoing monitoring by the staff to react to fault indication which may occur during the operation.
  • Page 8 User manual ZSP135-DR No. of documentation 0404.00.95-02.2 Page 8/12 Indication of faults relay yellow LED USZ BATERII Fault FAULT (BATTERY FLT) Mains power failure – including a failure of the converter Battery bank not present or voltage of the connected bank below 10V Low voltage (<24V) during battery test *1) High resistance (>250mΩ)of the battery circuit *1)
  • Page 9 User manual ZSP135-DR No. of documentation 0404.00.95-02.2 Page 9/12 4.5. Maintenance The device doesn’t require any special maintenance activities. During the normal operation one has to take care only to keep the necessary cleanness in the proximity of the box. It must be taken into consideration that if battery expected life is e.g.
  • Page 10 User manual ZSP135-DR No. of documentation 0404.00.95-02.2 Page 10/12 5.2. Diagnostics and correcting of malfunctions Each case of triggering the visual indication FAULT – except mains power failure and the failure of the is accompanied by the change of state of the relay (BATTERY FLT).
  • Page 11 User manual ZSP135-DR No. of documentation 0404.00.95-02.2 Page 11/12 6. Remarks on the selection of the type of the power supply Power supplies ZSP135-DR have various output currents and cooperate with internal batteries of various capacities. The selection of the specific type should depend on requirements of the specific load (powered devices).
  • Page 12 User manual ZSP135-DR No. of documentation 0404.00.95-02.2 Page 12/12 power supply. Owing to the module the power supply ZSP135-DR can be visible in the Building Management System GEMOS. The manufacturer offers integration with other systems. More information on the cooperating devices shall be found in their separate user manuals. 7.3.