USER MANUALS FOR POWER SUPPLY ZUP-230V
Power supply for fire alarm devices, heat and smoke control systems, fire protection and fire
ZUP-230V-400, ZUP-230V-700, ZUP-230V-1000, ZUP-230V-1500
Power supply for fire alarm devices, heat and smoke control systems, fire
designed to operate with the power supply ZUP-230V
The document contains:
USER MANUAL
automation systems.
USER MANUAL
protection devices and fire automation
ZSP121N-DR
14.05.2018
and
Nr dok. 0697.00.95-12.0

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ZUP-230V and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for MERAWEX ZUP-230V

  • Page 1 Power supply for fire alarm devices, heat and smoke control systems, fire protection and fire automation systems. ZUP-230V-400, ZUP-230V-700, ZUP-230V-1000, ZUP-230V-1500 USER MANUAL Power supply for fire alarm devices, heat and smoke control systems, fire protection devices and fire automation ZSP121N-DR designed to operate with the power supply ZUP-230V 14.05.2018...
  • Page 2: Table Of Contents

    USER MANUAL Power supply for fire alarm devices, heat and smoke control systems, fire protection and fire automation systems. ZUP-230V-400, ZUP-230V-700, ZUP-230V-1000, ZUP-230V-1500 Meeting the EN 54-4 and EN 12101-10 Certificate of constancy of performance CNBOP No. 1438-CPR-0593 Certificate of admittance CNBOP No. 3183/2018 14 May 2018 Technical description.
  • Page 3: Technical Description

    (e.g. fire alarm). Response times for individual types of outputs can be set by a user in a wide range by using slide switches. The main application of the ZUP-230V power supplies includes: •...
  • Page 4: Technical Data

    Weight with battery ZUP-230V-400 -700 -1000 42 kg 45Ah ZUP-230V-1500 65 kg 75Ah Fig.1. Dimensions and placement of mounting holes of ZUP-230V power supplies. Basic electrical and environmental parameters. Power Mains voltage 230V - 25% +10% 50Hz Outputs 230Vac *1)
  • Page 5: Construction

    User manual ZUP-230V Nr dok. 0697.00.95-02.3 4/15 - after disconnection of discharged battery 0.33mA Maximum, additional resistance in battery circuit Ri max. *6) 25mΩ/45Ah; 19mΩ/75Ah Environment Operating temperature -5…+40°C Level of security EN 60529:2003 IP 42 *1) The power and output circuits of 230Vac have the common conductor N.
  • Page 6 Nr dok. 0697.00.95-02.3 5/15 Fig.2. Simplified diagram of ZUP-230V power supplies. The 230V power distribution block (ZUP) switches the power outputs of the AC-1, AC 2, AC-3 and AC-4 external devices in accordance with their functions, while supplying the voltage from mains (230Vac power) or from the inverter in the event of power failure.
  • Page 7: Functioning Of Outputs

    Functioning of outputs. Note The basic operation of the 230 V outputs of the ZUP-230V power supply has been described below. It is possible, after prior arrangement, to produce such a version, in which outputs will present other time dependencies and in particular, several outputs will have the same functionality. This allows for direct connection of several loads, which should be powered in the same way.
  • Page 8 User manual ZUP-230V Nr dok. 0697.00.95-02.3 7/15 interrupted and the countdown of the T2 time begins. The time T3 results from the operation of the AC-4 output and it can range from 5 up to 65s. Warning. Separate use of T2 and T3 times is included in the AC-4 output description.
  • Page 9 User manual ZUP-230V Nr dok. 0697.00.95-02.3 8/15 FIRE ALARM MAINS POWER T2+T3 Operating from OUTPUT AC-3 BATTERY ~150ms Fig.5. Voltage timing for AC-3 output. If the voltage was present at the AC-3 output, it disappears after a fire alarm occurred for its duration, but not shorter than T2+T3 (see the description of the times of the AC-1 output).
  • Page 10: Description Of 230Vac Distribution Packet Of Zup Power Supply

    PR AC A IN W WYUSZ +INW +AKU TEST CSP PARA M Fig.7. View of 230Vac distribution packet of ZUP-230V power supplies. Description of 230Vac distribution packet components. Designation Description Connectors ZAS 230V 230Vac mains power input (*) WY INW...
  • Page 11: Installation

    User manual ZUP-230V Nr dok. 0697.00.95-02.3 10/15 - ON parameterization is required (10kΩ||1kΩ); - OFF parameterization is not required (ordinary binary input); - factory setting: OFF Jumper setting active state of CSP alarm: - jumper in L position or its absence: fire alarm active in low state;...
  • Page 12: Connecting Mains

    In this case, it is possible to use a soft starter system (so called soft- starter), for example, the ZUP-MS type of the MERAWEX. However, a user is asked to consult the manufacturer, due to different nature of loads, which may require setting individual device operation parameters.
  • Page 13: Connection Of Alarm Input From Fire Alarm Control Panel (Csp)

    User manual ZUP-230V Nr dok. 0697.00.95-02.3 12/15 own fuse, the common disconnector enables reliable disconnection of the battery from the entire power supply. All connections should be made carefully, remembering that during the battery operation (when no mains power) the current consumed by the inverter can reach up to 80A.
  • Page 14: Checking Basic Functions

    User manual ZUP-230V Nr dok. 0697.00.95-02.3 13/15 • in the initial state, the mains should be disconnected (with the installation switch outside the power supply) as well as the battery bank (W-BAT switch); • each activation of the power supply causes the LEDs to switch on for a moment: INW, ALP, T2+T3;...
  • Page 15: Setting Time

    User manual ZUP-230V Nr dok. 0697.00.95-02.3 14/15 – – Connecting additional 1kΩ resistor to CSP input – – – Disconnection of additional 1kΩ resistor from CSP – – after time T2+T3 With the parameterization of the fire alarm input set, its failure activates fault signalization, which should disappear after connecting a 10kΩ...
  • Page 16: User Manual Zup-230V Nr Dok. 0697.00.95-02.3

    User manual ZUP-230V Nr dok. 0697.00.95-02.3 15/15 The product packaging is made of materials that can be recycled (wood, paper, cardboard, plastics). Unnecessary packaging should be distributed to the recipient of the waste. This marking on the product indicates that the product should not be disposed of with municipal waste at the end of its usage time, but must be returned to the collection point for waste electronics.
  • Page 17: Toruńska

    Power supply for fire alarm devices, heat and smoke control systems, fire protection devices and fire automation ZSP121N-DR designed to operate with the power supply ZUP-230V 27 March 2018 Warnings Read all the tips and recommendations below. Failure to observe them can cause damage to the device, electric shock, fire or serious injury.
  • Page 18 User manual ZSP121N-DR Nr dok. 0696.00.95-02.0 Strona 2/8 Electrical parameters. Power 165…230…253V 50Hz Mains Power factor 0.66 Leakage current in the protective conductor 0.6mA Efficiency in nominal conditions Output Number of outputs Protection of outputs fuses 5x20mm 6.3AF Output voltage 21.0…28.8V (depending on battery condition and - with battery connected - without batteries...
  • Page 19 User manual ZSP121N-DR Nr dok. 0696.00.95-02.0 Strona 3/8 Binary inputs of external indications 3.3V/0.7mA, protection ±30V/50mA External signal input protection Input for connecting tamper switch (tamper) 3.3V/0.7mA *1) Markings acc. to EN 54-4 + A1 + A2 *2) Possibility of switching by a user. The limitation of the charging current and the threshold of the maximum resistance of the battery circuit are switched simultaneously.
  • Page 20 User manual ZSP121N-DR Nr dok. 0696.00.95-02.0 Strona 4/8 upwards. Mounting can be done in the reverse order, also without the use of a lever, by snapping the bracket on the rail. The power supply must be connected to a permanent installation by using a protective conductor and taking into account the L, N and PE markings.
  • Page 21 User manual ZSP121N-DR Nr dok. 0696.00.95-02.0 Strona 5/8 Description of ZSP121N-DR power supply elements Recommended type and cross- Item Description Marking section of wire 3-wire cable of HDGs type 0.75 ... Connector of 230V 50Hz mains L, N, PE 1.5mm Additional protective terminal Mains switch Mains fuse...
  • Page 22 User manual ZSP121N-DR Nr dok. 0696.00.95-02.0 Strona 6/8 First start If all connections have been made correctly after connecting the power supply to the mains, the green signalization diode on the power supply packet and the diode of the eternal MAINS MAINS indication should be on.
  • Page 23 User manual ZSP121N-DR Nr dok. 0696.00.95-02.0 Strona 7/8 supplies in new facilities. In this case, it is advisable to disconnect the batteries from the power supply for that time. External fault signalization input - terminals on EXT FLT connector The power supply can receive one external binary signal. It can be an active signal of 0V/5V or potential-free relay contacts.
  • Page 24 User manual ZSP121N-DR Nr dok. 0696.00.95-02.0 Strona 8/8 Appendix LED signalization, outside the power supply. Reaction green LEDdiode MAINS time - no mains, battery disconnected (no-voltage condition) - mains on, rectifier operational 0/1 pulsowanie - battery operation (no mains or rectifier faulty) FAULT yellow LED diode - no faults...