Diagnostic Event - Parker 2003-IP-00 Technical Manual

Ethernet/ip– communication option
Hide thumbs Also See for 2003-IP-00:
Table of Contents

Advertisement

DOC-0017-08-EN: AC20 Series Ethernet/IP Option

13 Diagnostic Event

Configuration problems can often be identified by looking at the Run and Error LEDs and from the Comms
Diagnostic 0775 parameters. Under normal operating conditions the Comms diagnostic parameter should
indicate OK. Other values are summarized in the Diagnostic Parameters section.
Hardware Mismatch
Diagnostic = HARDWARE MISMATCH:
The required option does not match the actual fitted option.
No option is fitted but one is required.
Invalid Configuration
Diagnostic = INVALID CONFIGURATION:
Invalid read or write process data mapping
Invalid communication settings
Diagnostic = MAPPING FAILED:
Attempting to map a parameter that does not exist.
Attempting to map a configuration parameter.
Attempting to map a read-only parameter to the read process data.
Other Diagnostics
Diagnostic = EXCEPTION :
Module has gone into an unrecoverable exception state
Diagnostic = UNSUPPORTED OPTION:
The fitted option is not supported by the drive
Diagnostic = NOT RESPONDING:
no initial response from the option