INTENDED USE device. All Vallox ventilation units have been designed to provide appropriate and continuous ventilation so as to present no threat to health and to maintain structures in good condition. IMPORTANT...
INSTALLATION OPTIONS NOTE The standard equipment and • Vallox 101 MV can be mounted either on the wall, or on the ceiling available accessories by using a mounting plate (optional). vary from country to country. SYSTEM DESCRIPTION Internet 2.
NOTE For the MyVallox Cloud/ Home instructions, Ventilation unit control options please go to vallox.techmanuals.info/ Operation of the Vallox ventilation unit can be controlled by the ValloxMV/ENG/help/ following means: webhelp • Through the MyVallox control panel installed in the building.
MAIN PARTS R model in the figure Post-heatingresistor (in the supply air duct) Extract air fan Safety switch Internal carbon dioxide and Supply air fan humidity sensor Fine filter for supply air Control panel Heat recovery cell Carbon dioxide sensor (optional) Bypass damper of the HR cell Humidity sensor (optional) Coarse filter for supply air...
+10°C. MOUNTING ON THE CEILING Vallox 101 MV can be equipped with an optional ceiling mount plate. To attach the ceiling mounting plate: • On rafter frames or other frame structure with M8 thread bars so that they withstand the weight of the unit.
Installing the ventilation unit to the ceiling mounting plate Install the ceiling mounting plate with M8 thread bars so that it is horizontally level. NOTE The end of the thread bars must be 5 mm or less below the fastening nut. Do not fasten the ceiling mounting plate too tight to the ceiling.
147,5 be moved to the pipe connection part that is mounted on the wall. Space required by the alternative Vallox Silent Klick siphon installation method (elbow) MEASURING AND ADJUSTING THE AIR FLOWS OF THE VENTILATION UNIT The accessories delivered with the unit include four (4) air flow measuring tubes.
DIMENSIONS AND DUCT OUTLETS Main parts Dimensions and duct outlets Dimensions 461,5 136,5 R model in the figure. In the L model, the parts are mirrored 154,5 443,5 6. Coarse filter for supply air 1. Extract air fan 7. Coarse filter for extract air 2.
Disconnect the ventilation unit from the mains 555 mm. electricity supply. 2. Open the door of the Vallox ventilation unit by undoing the finger screws. 3. Lift the door off. 4. Remove the old filters (A, B, C) and discard them.
To check and clean the heat recovery cell: Disconnect the ventilation unit from the mains electricity supply. 2. Open the door of the Vallox ventilation unit by undoing the finger screws. 3. Lift the door off. CAUTION The door is heavy.
To clean the fan: them. Disconnect the ventilation unit from the mains electricity supply. Handle the fan blades 2. Open the door of the Vallox ventilation unit by undoing the carefully. Do not finger screws. remove or move the 3. Lift the door off.
Air flow dm³/s 15/20 24/30 33/40 42/48 52/58 61/68 70/76 78/84 83/89 Air flow m³/h 54/72 86/108 119/144 151/173 187/209 220/245 252/274 281/302 299/320 , dB (A) You can calculate the sound values for each operating point with the Vallox MySelecta software.
DUCT RADIATOR OPERATION Always follow first and foremost the connection diagram provided by the HVAC designer or heat pump manufacturer. If the duct NOTE: Also read the duct radiator manual. radiator is used in the supply air duct, it The accompanying figure shows an example of the can only be used for arrangement for connecting the heating/cooling radiator unit cooling.
Feed from the distribution board External electrical junction box for the MV Air extraction External NTC sensor for Vallox MV ventilation units Duct radiator (reverse connection) 24 VDC relay/contactor for controlling the pump and the solenoid valve. Not included in the delivery.