Installation, operating and maintenance instructions
English
DHN...D.F4
Example configuration shown
CONTENTS
FOREWORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.
IMPORTANT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.
GENERAL SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
3.
ADHERE TO THE FOLLOWING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4.
PRODUCT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5.
DELIVERY CONTENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6.
TECHNICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
7.
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
8.
9.
TRANSPORT AND STORAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
10.
ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
11.
ELECTRICAL CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
12.
COMMISSIONING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
13.
MAINTENANCE AND CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
14.
LIFETIME AND DISPOSAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
15.
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
16.
ruck Ventilatoren GmbH
Max-Planck-Str. 5
D-97944 Boxberg-Windischbuch
Tel.
+49 (0)7930 9211-300
Fax
+49 (0)7930 9211-166
info@ruck.eu
www.ruck.eu
Smoke extract fan
for exhaust air ap-
plications
The original instructions were created in the German language.
2018
Information updated
print 12.09.2019
Subject to change
www.ruck.eu

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DHN D F4 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Ruck Ventilatoren DHN D F4 Series

  • Page 1: Table Of Contents

    TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 ruck Ventilatoren GmbH Max-Planck-Str.
  • Page 2: Foreword

    FOREWORD Dear customers, Thank you for choosing our device. Before operating the unit, please read carefully these installation, operating and maintenance instructions. If you have any questions, please contact: (Contact details see page 1) The data provided in these installation, operating and maintenance instructions are for the product description only. A statement about a certain condition or a suitability for a certain application cannot be derived from our information.
  • Page 3: General Safety Instructions

    2.2. Provisions and regulations When properly installed and operated, the device complies with the applicable standards and EU Directive at the time of its placing on the market. In addition, observe generally valid, legal and other binding regulations of the European or national legislation as well as the regulations in your country for accident prevention and environmental protection.
  • Page 4 3.1. Intended use Our devices are incomplete machineries as defined in the EU Machinery Directive 2006/42/EC (partly completed ma- chinery). The product is a not ready-for-use machine in terms of the machine directive. It is intended exclusively for installation in a machine or in ventilation equipment and installations or for combination with other components to form a machinery or installation.
  • Page 5 Safety sign (warning Consequence triangle) General warning! Indicates possible hazardous situations. Failure to observe the warnings may result in perso- nal injury and / or damage to property. Electricity warning (hazardous voltage)! Indicates possible hazards due to electricity. Failure to observe the warnings may result in death, injury and/or damage to property.
  • Page 6: Adhere To The Following Instructions

    ADHERE TO THE FOLLOWING INSTRUCTIONS 4.1. General instructions ■ Persons who assemble, operate, disassemble or maintain our devices must not be under the influence of alcohol, drugs or pharmaceuticals that may affect perception and responsiveness. ■ Responsibilities for the operation, maintenance and regulation of the product should be clearly determined and observed so that there can be no unclear areas of responsibility with regard to safety.
  • Page 7: Delivery Contents

    DHN...D.F4 Roof fans 200 °C - vertical discharge 3.000-31.500 m³/h, with backward curved impeller blades 5.1. Permissible conveying medium temperatures perm. temperature perm. temperature in time in smoke extraction continuous operation Series ■ DVN...D.F4 +400°C / 120 min -20°C bis +200°C 5.2.
  • Page 8: Technical Data

    TECHNICAL DATA Product name °C °C dB(A) dB(A) DHN 225 D2 F4 30 150593 400V 3~Y 150251 19,1 DHN 250 D2 F4 30 150559 400V 3~Y 150251 20,0 DHN 280 D2 F4 30 150695 400V 3~Y 150251 23,7 DHN 315 D2 F4 30 150555 400V 3~Y 1145...
  • Page 9: Data In Accordance With Erp Directive 327/2011 Of The European Parliament

    ! Year of manufacture see nameplate Manufacturer name / Commercial registration number / Place of establishment ruck Ventilatoren GmbH / Local District Court Mannheim HRB 560366 / Germany Nominal motor power input at optimum energy efficiency point P [kW] 0,33...
  • Page 10: Transport And Storage

    10. TRANSPORT AND STORAGE Transport and storage should only be performed by specialist personnel in accordance with the assembly and opera- ting manual and regulations in force. The following points should be noted and followed: ■ Check the delivery according to the delivery note to ensure it is complete and correct and check for any damage. Any missing quantities or damage incurred during transport should be confirmed by the carrier.
  • Page 11 11.1. Mounting on roof socket (DSF) ■ Release screws (1) and washers (2) on both sides ■ Mount the nozzle plate (3) with hexagonal screws and sealing washers (4)+(5) on roof socket (DSF) ■ (If required, it is possible to install further accessories at this point, see 11.3 Installation examples with accesso- ries) ■...
  • Page 12 11.3. Installation examples Roof fan Roof fan Tube Tube Tube Roof fan Roof fan Tube Tube 12 | DHN...D.F4 Installation, operating and maintenance instructions...
  • Page 13: Electrical Connection

    12. ELECTRICAL CONNECTION • Electricity warning (hazardous voltage)! » Failure to observe the hazard may result in death, injury or damage to property. → Before performing any work on conductive parts, always disconnect the unit completely from the electri- city supply and make sure that it cannot be switched back on again. The electrical installation may only be carried out by qualified electricians in compliance with the installation, operating and maintenance instructions and the applicable national regulations, standards and guidelines: ■...
  • Page 14 The following connections are only possible for sizes 225 ... 560: ■ Star circuit (Delivery status) The star circuit must be used if the motor is to be operated directly on the 3-pha- se supply network with a line voltage of 400V.
  • Page 15: Commissioning

    12.6. Frequency converter If the fans are placed on the EU market or operated within the EU, they must have a speed control. This is only possible by means of frequency converters. Using other speed controls, such as voltage control, will directly damage the motor. We offer tested and approved frequency converters as accessories.
  • Page 16: Maintenance And Cleaning

    Note: Standard frequency inverters have a modified sine-wave at the output. This may cause noises, depending on the com- bination motor - frequency converter. Depending on the fan design and the radiating surface, these are perceptible. At very high noise requirements, this can be disturbing. For industrial applications, the noises are generally acceptable. Remedial measures may be a change in the clock frequency or the use of a sine-wave filter or a frequency converter with integrated sine-wave filter.
  • Page 17 14.1. Checklist Maintenance and Service Description check interval Triggering device monthly ■ Fan Check fan for function and operational readiness (test run at least 15 minutes) every 6 months Check fan for function and operational readiness (test run at least 1 hour) yearly Check for dirt, damage, corrosion and fastening every 6 months...
  • Page 18: Lifetime And Disposal

    Technical data Bushing size Torque table Bushing size 1210 2012 2517 Screw tightening torque with feather (Nm) Screw tightening torque without feather (Nm) Number of screws Commissioning (after replacement) ■ Remove any remaining installation material and foreign objects from the impeller and suction area. ■...
  • Page 19: Troubleshooting

    16. TROUBLESHOOTING Fault Possible cause Remedy methods ■ Fan does not start ■ No power supply ■ Check mains supply / connections ■ Impeller does not rotate freely ■ Find out the causes and, if possible, remove the fault. If not possible, contact the sup- plier.