EPS PSI 10000 4U Operating Manual

Dc high efficiency power supply
Hide thumbs Also See for PSI 10000 4U:
Table of Contents

Advertisement

Quick Links

Operating Guide
PSI 10000 4U
DC High Efficiency Power Supply

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PSI 10000 4U and is the answer not in the manual?

Questions and answers

Summary of Contents for EPS PSI 10000 4U

  • Page 1 Operating Guide PSI 10000 4U DC High Efficiency Power Supply...
  • Page 2: Table Of Contents

    3.5.2 Control locations Installation 3.5.3 Remote control via a digital interface 2.3.1 Safety procedures before installation and use 29 3.5.4 Remote control via the analog interface © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 3 Attention! The part of this document that deals with the handling of features on the control panel is only valid for devices with firmwares “KE: 3.02”, “HMI: 3.02” and “DR: 1.0.2.20” or higher. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 4: General

    Symbol for general notices Warranty EPS Stromversorgung guarantees the functional competence of the applied technology and the stated performance param- eters. The warranty period begins with the delivery of free from defects equipment. Terms of guarantee are included in the general terms and conditions (TOS) of EPS Stromversorgung.
  • Page 5: Disposal Of Equipment

    Maximum current of the device in Ampere Maximum voltage of the device in Volt („10080“ = 80 Volt) Series: 10 = Series 10000 Type identification: PSI = Power Supply Intelligent © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 6: Intended Usage

    Read and understand the operat- ing guide before using this device. Non-adherence of the instructions in the operating guide can result in serious injury or death. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 7: Safety

    (also see “3.4. Manual operation“ and “3.4.3. Configuration via the menu“ ) © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 8: Responsibility Of The Operator

    • Furthermore, anyone working with the equipment is responsible for ensuring that the device is at all times technically fit for use. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 9: Alarm Signals

    Only if the current and voltage are supplied by the device as adjustable in the range of 0-100% FS, the device can be consid- ered as correctly operational. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 10: Technical Data

    1.8.2 General technical data Display: Color TFT touch screen with gorilla glass, 5”, 800pt x 480pt, capacitive Controls: 2 rotary knobs with pushbutton function, 1 pushbutton © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 11: Specific Technical Data

    0 - 10 V: ≤0.2%, 0 - 5 V: ≤0.4% *1 Models up to 80 V DC rating have reinforced insulation while all other models from 200 V DC rating have basic insulation © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 12 Enclosure: 19“ x 4U x 668 mm (26.3 in) Total: 19“ x 4U x min. 785 mm (31 in) Weight 50 kg (110 lb) Weight with water cooling 56 kg (126 lb) © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 13 +2000 V DC Article numbers Standard 06230804 06230805 06230809 06230806 Standard + Water Cooling 06250804 06250805 06250809 06250806 *1 At 100% power and 100% output voltage © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 14 Positive DC pole <-> PE +2000 V DC +2000 V DC Article numbers Standard 06230807 06230808 Standard + Water Cooling 06250807 06250808 *1 At 100% power and 100% output voltage © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 15: Views

    1.8.4 Views 1.8.4.1 Technical Drawing PSI 10000 4U ≤200 V © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 16 6. Mains input terminal 7. Grounding connection screw (PE) 8. Connector (DB15 female) for isolated analog programming, monitoring and other functions 9. USB interface 10. Ethernet interface © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 17 1.8.4.4 Technical Drawing PSI 10000 4U >360 V © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 18 6. Mains input terminal 7. Grounding connection screw (PE) 8. Connector (DB15 female) for isolated analog programming, monitoring and other functions 9. USB interface 10. Ethernet interface © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 19 7. Mains input terminal 8. Grounding connection screw (PE) 9. Connector (DB15 Female) for isolated analog programming, monitoring and other functions 10. USB interface 11. Ethernet interface © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 20: Control Elements

    DC output, no matter if the device is manually controlled or remotely. Port for USB sticks For the connection of standard USB sticks. See section “1.9.6.5. USB port (front side)“ for more details. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 21: Construction And Function

    General description The electronic high performance power supplies of the PSI 10000 4U series are especially suitable for industrial test which have a demand for high power. All models in this series have a rated power of 30 kW and offer high currents or high voltages to cover a broad spectrum of applications.
  • Page 22: Scope Of Delivery

    Water cooling the environment due to exhausted heat caused by a certain power dissipation. As a side effect, this type of cooling also reduces audible noise. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 23: The Control Panel (Hmi)

    Protection settings ditto 0-110% nom OVP, OCP etc., related to the physical values The lower limit for resistance set value varies. See tables in section 1.8.3 © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 24 Pushbutton function of the knobs The rotary knobs also have a pushbutton function which is used in all value adjustment to move the cursor by rotation as shown: © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 25 File with log data recorded during normal operation in all modes. The file layout is identical to the those generated from the Logging feature in EPS Power Control. The <nr> field in the file name is automatically counted up if equally named files already exist in the folder.
  • Page 26: Usb Port (Rear Side)

    0-5 V and 0-10 V, in each case for 0-100%. Figure 4 - Analog interface © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 27: Share Bus" Connector

    1200 m, but it’s recommended to keep the con- nections as short as possible. Figure 7 - Master slave bus ports © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 28: Ethernet Port

    The water taps are located on the rear side of the device, also see the rear view drawing in section 1.8.4 . Details about the connection, requirements and use of the water cooling can be found in section 2.3.4 . © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 29: Installation & Commissioning

    Continuous operation at the approved limit generates heat which must be removed, as well as voltage • loss which depends on cable length and heating. To compensate for these the cable cross section should be increased and the cable length reduced. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 30: Installing The Device

    The required air flow would be insufficient. This wouldn’t actually apply to water cooled models, but the construction of the entire device isn’t made for operation in this position. Acceptable and unacceptable installation positions (air or water cooled, air cooled shown): Standing surface © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 31: Installing The Water Cooling

    24.31 25.16 27°C 14.08 15.68 17.24 18.57 19.83 21.11 22.23 23.31 24.32 25.22 26.1 28°C 14.96 16.61 18.14 19.38 20.86 22.07 23.18 24.28 25.25 26.2 27.18 © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 32 118.3 120.2 2.3.4.4 Notes • The water flow should be started prior to powering the device, but at least prior to switching the DC terminal on © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 33: Connection To Ac Supply

    Stripping length without cable end sleeve: 18-20 mm (0.75 in) • Valid for both, the ground conductor in the AC cable and the separate PE line for enclosure grounding © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 34 (cabinet), it’s recommended to only pull the plug and dismount the bracket. Figure 10 - Mounting position of the bracket Figure 11 - Fully installed strain relief © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 35 AC cable. It’s done be laying a separate protective earth line (PE) of the same or higher cross section as in the AC cable and connected here. Figure 12 - Grounding point © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 36: Connection To Dc Loads

    M10 bolt on a metal rail M6 bolt on a metal rail Recommendation: ring lug with a 11 mm hole Recommendation: ring lug with a 6.5 mm hole © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 37: Grounding Of The Dc Output

    In case any DC pole is grounded, the operator of the device must reinstate the basic protection for human safety by installing appropriate external means, for instance a cover, everywhere the potential of the DC terminal is connected to. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 38: Connection Of Remote Sense

    Dangerous voltage on the sense terminals! The sense cover must always be installed. Figure 13 - Example for remote sensing wiring (DC terminal and Sense terminal covers left way for illustrative purposes) Allowed connection schemes: © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 39: Installation Of An Interface Module

    On the bottom side of the module are two plastic nibs which must click into the green board (PCB) so that the module is properly aligned on the rear wall of the device. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 40: Connecting The Analog Interface

    Refer to “2.3.13. Initial commission“ . Only after successful checking of the device as listed may it be operated as usual. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 41: Operation And Application

    = transient time to below the adjusted value for a short time. t = transient time settle the output voltage. to settle the output voltage. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 42: Current Regulation / Constant Current / Current Limiting

    With resistance mode being activated the function generator will be unavailable and the actual power value provided by the device does not include the simulated power dissipation of Ri. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 43: Alarm Conditions

    DC output reaches the adjusted OPP limit. • This function serves to protect the connected load application so that this isn’t overloaded and possibly damaged due to an excessive power consumption. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 44: Safety Ovp

    This alarm has to be acknowledged after the cause has been removed. Should the device neither be master nor slave, the Share bus cable should be removed for unimpeded operation. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 45: Manual Operation

    Many settings are self-explanatory, others are not. Those will be explained on the pages following. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 46 = Levels and function as described in the table in 3.5.4.3 • Inverted = Levels and function will be inverted • Also see “3.5.4.7. Application examples“ . © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 47 Determines the condition of the DC output after leaving remote control either manually or by command: = Default, DC output will always be off after leaving remote control • • Auto = DC output will keep the last state © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 48 = Logging starts and stops with every change of state on the DC output, no matter if • caused by the user, software or a device alarm. Attention: Every next start will create a new log file. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 49 = Baud rate and node address are assigned by the bus master Fixed baud rates: kbps, kbps, kbps, kbps, kbps, kbps, kbps, kbps, 1Mbps Node Address Selection of the CANopen node address in the range 1...127 © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 50 String input box for a user-definable text which describes the Profibus slave. Max. length: 54 characters Station Name String input box for a user-definable text which describes the Profinet station name. Max. length: 200 characters © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 51 The baud rate is selectable, other serial settings can’t be changed and are defined like this: 8 data bits, 1 stop bit, parity = none Baud rates: 2400Bd, 4800Bd, 9600Bd, 19200Bd, 38400Bd, 57600Bd, 115200Bd © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 52 Furthermore, the backlight intensity can be adjusted here. Lock See “ “3.8. Locking the adjustment limits and user profiles“ and “3.9. Loading and saving user profiles“ © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 53: Adjustment Limits

    The actual operating mode, which is only indicated while the DC output is switched on, solely depends on the set values. For more information see section “3.2. Operating modes“. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 54: Manual Adjustment Of Set Values

    The display then switches back to the main page and the set values take effect. When entering a value which would exceed the upper/lower adjustment limit it would be rejected with an appropriate message. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 55: Switching The Dc Output On Or Off

    The logging stores files of CSV format on the stick where the layout of the log data is the same as when logging via PC with software EPS Power Control. The advantage of USB logging over PC logging is the mobility and that no PC is required. The logging feature just has to be activated and configured in the Settings.
  • Page 56: The Quick Menu

    The device offers a quick menu which allows for the quick access to often used features and modes being switched on or off in the Settings menu. It can be opened by swiping up from the bottom screen edge or tapping the bar: Overview: © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 57: The Graph

    Swiping on the three scales (Y axis) moves them up or down • Tapping the menu touch area ( ) exits the graph screen anytime • © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 58: Remote Control

    Programming details for the interfaces, the communication protocols etc. are to be found in the documentation “Programming Guide ModBus & SCPI“ which is supplied on the included USB stick or which is available as download from the manufacturer’s website. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 59 The timeout of the monitoring can be changed anytime via remote control; the new value would only be valid after the • current timeout has elapsed The interface monitoring doesn’t deactivate the Ethernet connection timeout (see 3.4.3.6 ), so these two timeouts can overlap • © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 60: Remote Control Via The Analog Interface

    PF and OVP being signaled at the same time, so it would require to select the alarm indication on pin 6 to at least signal PF and for pin 14 to signal OVP in any of the combinations. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 61 The resolution is the same for set values (VSEL etc.) and actual values (VMON/CMON) and is 26214 when working with the 10 V range. In the 5 V range this resolution halves. Due to tolerances, the truly achievable resolution can be slightly lower. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 62 -> REM-SB level” being set to “Normal”, it requests to switch the DC output on. So when activating remote control, the DC output will instantly switch on. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 63 The AI provides the actual values on the DC output as current and voltage monitor. These can be read using a standard multimeter or an analog input of a PLC etc. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 64: Alarms And Monitoring

    The DC output will be switched off. OverPower Triggers an alarm as soon as the DC output power reaches the OPP 0 W...1.1*P Protection threshold. The DC output will be switched off. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 65 Swipe with your finger up from the bottom edge of the screen or directly tap on the bottom bar: The quick menu will open. Tap on to activate the alarm sound, or on to deactivate it. Leave the quick menu. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 66 User events are part of the currently selected user profile. Thus, if another user profile or the default profile is loaded, the events could either be differently configured or not at all. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 67: Locking The Control Panel (Hmi)

    In the group tap on Unlock limits and profiles. You will be requested to enter the 4-digit PIN. Deactivate the lock by entering the correct PIN. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 68: Loading And Saving User Profiles

    Loading a user profile works the same way, but in the requester you would then tap Load under Load profile?. Alternatively, you may import the profile or export it as file to an USB stick with Import/Export. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 69: The Function Generator

    DC output could be improved by attaching and additional load (fixed & ohmic or variable & elec- tronic) to the actual one, which can significantly improve down-ramping. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 70: Method Of Operation

    “U/I/P limits”. These limits are transferred to all slave units of master-slave systems. It’s recommended to carefully configure them so the MS system can work as expected and the slaves wouldn’t impact the function run in a negative way. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 71: Manual Operation

    Any device alarm (power fail, overtemperature etc.), protection (OPP, OCP) or event with Action = Alarm stops the function progress automatically, switches off the DC output and reports the alarm. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 72: Sine Wave Function

    100 ms. This 100 ms can be freely allocated to t1 and t2, e.g. 50 ms:50 ms (isosceles triangle) or 99.9 ms:0.1 ms (right-angled triangle or sawtooth). © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 73: Rectangular Function

    The periodic duration and repetition frequency are the result of four time elements. With suitable settings the trapezium can be deformed to two triangular or two rectangular pulses. It has, therefore, universal use. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 74: Din 40839 Function

    Start/end frequency of the sinusoidal AC part End frequency Angle 0°...359° Start angle of the sinusoidal AC part Time 0.1 ms...36,000,000 ms Time for the selected sequence © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 75 180°. The start angle can be shifted at will in 1° steps between 0° and 359°. Start (AC) Start (AC) End (AC) End (AC) Seq.time Seq.time © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 76 This can produce a discontinuity in the total progression (marked in red) which may only be compensated with careful choice of settings. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 77 End frequency 0...10000 Hz Angle 0...359° See table in “3.10.10. Arbitrary function“ DC start DC end See table in “3.10.10. Arbitrary function“ Time 100...36.000.000.000 (36 billion μs) © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 78 In the file open dialog you can either select an existing file, if at least one compatible file is listed, or you can create a new one by not selecting any file. Save the file, new or overwriting, with © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 79: Ramp Function

    0 A and the other maximum current. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 80 (also see “3.10.4.1. Func- Finally proceed to the main function screen with tion selection and control“). © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 81: Simple Pv (Photovoltaics) Function

    (no power output) to the minimal amount of light that is required to have the panel provide full power. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 82: Fc Table Function (Fuel Cell)

    In order to express the rules in a simplified way: the voltage has to decrease from point 1 to point 4, while the current has to increase. In case the rules are not followed, the device will reject the settings with an error and reset them to 0. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 83 Without any load, the voltage will rise to the adjusted Uoc value. Stop the function run anytime by the stop button or by switching off the DC output. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 84: Extended Pv Function According To En 50530

    DAY E/T Automatic simulation run, processing a day trend curve consisting of up to 100,000 points defined by values for irradiation, temperature and time. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 85 The intermediate steps also respect the slope between the current and the next day trend curve point and thus every step • also includes a corresponding value alteration © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 86 “USB decimal point format” selects whether the device saves the CSV with comma (US) or semicolon (Standard) and defines the decimal point (dot and comma). The example CSV above shows the european format with decimal comma. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 87 Step 3: Select simulation mode For a description of the available simulation modes see 3.10.15.4 . When selecting the configuration continues with Step 4, otherwise an additional step is required © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 88 The data can later be used to visualize, analyze and determine characteristics of the simulated solar panel and also of the solar inverter which is usually used as load when running such tests. More details can be found in the standard paper. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 89: Remote Control Of The Function Generator

    REM-SB switching the DC output off and on, which will also stop and restart the function The function generator is unavailable if R mode (resistance) is activated • © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 90: Other Applications

    The same applies when building several blocks of devices, i. e. a block of power supplies and a block of elec- tronic load, to later connect then in two-quadrant operation. The blocks should be placed as close as possible to each other. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 91 Device position Termination setting(s) Master (at end of bus) BIAS + TERM Master (central in bus) BIAS Slave (at end of bus) TERM Slave (central in bus) © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 92 As long as MS mode remains activated, the initialization process of the master-slave system will be re- peated each time the master unit is powered. The initialization can also be repeated manually anytime via the Settings menu, in group “Master-Slave”. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 93 OCP alarm though the global OCP limit of the MS system was not reached. The same can occur with the OPP alarm. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 94: Series Connection

    SEMI F47 it’s delayed for at least 2 seconds or will never occur. In this case, the device wouldn’t show any reaction to the sag, nor register the occurrence in any form. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 95: Service And Maintenance

    The firmware of the control panel (HMI), of the communication unit (KE) and the digital controller (DR), if necessary, is updated via the rear side USB port. For this the software EPS Power Control is needed which is included with the device or available as download from our website together with the firmware update, or upon request.
  • Page 96: Trouble-Shooting Device Problems

    As an additional measure include fuses in line with the DC cables which could attenuate or even prevent damage to the device. © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...
  • Page 97: Contact And Support

    Headquarter eMail addresses Telephone EPS Stromversorgung GmbH All issues: Switchboard: +49 821 / 570451-0 Alter Postweg 101 info@eps-germany.de 86159 Augsburg Germany © EPS Stromversorgung in 2022, this information is subject to change without notice 06230800_manual_psi_10000_4u_30kw_en_03...