I Safety Precaution; Safety Precaution; Always Observe For Safety; Cautions Related To New Refrigerant - Mitsubishi Electric Mr.SLIM SFZ Series Technical & Service Manual

Table of Contents

Advertisement

[ I SAFETY PRECAUTION ]

[1] SAFETY PRECAUTION

I SAFETY PRECAUTION
MEANINGS OF SYMBOLS DISPLAYED ON THE UNIT
WARNING
(Risk of fire)
Read the OPERATION MANUAL carefully before operation.
Service personnel are required to carefully read the OPERATION MANUAL and INSTALLATION MANUAL before operation.
Further information is available in the OPERATION MANUAL, INSTALLATION MANUAL, and the like.

1. Always observe for safety

Before obtaining access to terminal, all supply circuits must be disconnected.

2. Cautions related to new refrigerant

Cautions for units utilizing refrigerant R32
Use new refrigerant pipes.
In case of using the existing pipes for R22, be careful with
the following.
· Be sure to clean the pipes and make sure that the insides
of the pipes are clean.
· Change flare nut to the one provided with this product.
Use a newly flared pipe.
· Avoid using thin pipes.
· In case of reconnecting the refrigerant pipes after
detaching, make the flared part of pipe re-fabricated.
Make sure that the inside and outside of refrige-
rant piping is clean and it has no contaminants
such as sulfur, oxides, dirt, shaving particles, etc,
which are hazard to refrigerant cycle.
In addition, use pipes with specified thickness.
Contamination inside refrigerant piping can cause deterio-
ration of refrigerant oil, etc.
Store the piping indoors, and keep both ends of
the piping sealed until just before brazing.
(Leave elbow joints, etc. in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of com-
pressor.
The refrigerant oil applied to flare and flange
connections must be ester oil, ether oil or
alkylbenzene oil in a small amount.
If large amount of mineral oil enters, that can cause deterio-
ration of refrigerant oil, etc.
Charge refrigerant from liquid phase of gas
cylinder.
If the refrigerant is charged from gas phase, composition
change may occur in refrigerant and the efficiency will be
lowered.
HWE1909A
This symbol is only for R32 refrigerant. The type of the refrigerant used is written on the nameplate on the outdoor unit.
R32 refrigerant is flammable. If the refrigerant leaks, or comes in contact with fire or parts that generate heat, it may
create harmful gas and pose a risk of fire.
Use a vacuum pump with a reverse flow check
valve.
Vacuum pump oil may flow back into refrigerant cycle and
that can cause deterioration of refrigerant oil, etc.
Use the following tools specifically designed for
use with R32 refrigerant.
The following tools are necessary to use R32 refrigerant.
Gauge manifold
Charge hose
Gas leak detector
Torque wrench
Handle tools with care.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of com-
pressor.
Do not use a charging cylinder.
If a charging cylinder is used, the composition of refrigera-
nt will change and the efficiency will be lowered.
Use the specified refrigerant only.
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the
unit is being used, serviced, or disposed of.
Correct refrigerant is specified on name plate of outdoor
unit.
If other refrigerant (R22, etc.) is used, chlorine in refrige-
rant can cause deterioration of refrigerant oil, etc.
We will not be held responsible for mechanical failure,
system malfunction, unit breakdown or accidents caused
by failure to follow the instructions.
Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
a flame, poisonous gases will be released.
- 1 -
Tools for R32
Flare tool
Size adjustment gauge
Vacuum pump adaptor
Electronic refrigerant
charging scale
GB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mr.slim sfz-m25vaMr.slim sfz-m25va-etMr.slim sfz-m35vaMr.slim sfz-m35va-etMr.slim sfz-m50vaMr.slim sfz-m50va-et ... Show all

Table of Contents