Table 10-2 Setting the external static pressure
Indoor unit type
15, 22, 28, 36,
90, 106
45, 56, 60, 73
External static pressure of the rated
airflow volume (Pa)
150
150
140
140
130
130
120
120
110
110
90
90
70
70
50
40 *
30 *
30
10
10
No auto airflow volume setting
Auto airflow volume setting
* Airflow volume setting at shipment
NOTE:
Failure to set this parameter may result in decreased airflow and condensation.
6. Select the "Unit no." by pressing the
and press the
The "Exit detailed settings and restart?" (Detailed setting-
end) screen appears on the LCD display.
Select "YES" and press the
When the setting is completed, perform the test run for the
external static pressure setting described in "Auto External
Static Pressure Setting Operation".
Auto External Static Pressure Setting Operation
7. Keep pressing the
simultaneously for 4 or more seconds.
The "Maintenance func" screen appears on the LCD
display.
8. Press the
If you wish to see the next screen instantly, press the
or
Select "4. Test run" on the LCD display and press the
button.
The "Test run" screen appears on the LCD display.
Item code
112, 140,
160
B0
150
0010
140
0009
130
0008
120
0007
110
0006
90
0005
70
0004
50 *
0003
30
0002
10
0001
-001
-002
button.
,
and
or
button to see each menu.
button.
or
button
button.
buttons
46
Detailed settings
20:30 (THU)
Exit detailed settings
Unit no.
Code no.
Set data
and restart?
ALL
01
0002
YES
NO
Sel.
Next
Maintenance func
20:30 (THU)
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4. Test run
Sel.
Page [
] Confirm
Maintenance func
20:30 (THU)
1. Outdoor unit error data
2. Service contact
3. RC setting mode
4. Test run
Sel.
Page [
] Confirm
Test run
20:30 (THU)
Test run
OFF
Change
[
] Confirm

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents