Panasonic S-15MF3E5AN Installation Instructions Manual page 42

Hide thumbs Also See for S-15MF3E5AN:
Table of Contents

Advertisement

Flow of External Static Pressure
Start external static pressure
setting
Line A (set at shipment)
on the PQ diagram was designed
and installed.
Yes
a. No setting modification
Operation checks for external static pressure settings (*Note (2))
See Section "10-2, 10-3 or 10-4".
Check if the setting is within the range of use on the PQ diagram.
If out of range, adjust until it becomes within the range of use.
In the case of identical setup, it is possible to omit this operation check if judged
unnecessary.
NOT E
(1) Check the following items before performing the setting-check operations or auto airflow
volume operations.
1) Check to make sure that the electrical wiring and ducting have been completed. Activate
the stand-by mode. In particular, make sure that the closed damper located in the middle
of the duct is open, if installed. Also, make sure that air filters have been installed inside
the air inlet duct.
Check to make sure air is not leaking from the joints.
Finish the ducting and electrical wiring and prepare it for use. (Note (1))
External static pressure should be set during initial operations after
installation (before the cooling and heating test run).
When operating with group control (connecting multiple indoor units with one
wired remote controller), make the middle static pressure duct type to the
main unit.
No
No
b. Manual setting
(set with the indoor unit
control PCB)
Change the dip switch.
See Section "10-1".
Test operation display will disappear. (*Note (6))
External static pressure setting completed
Set static pressure setting
to manual setting mode.
Yes
Wired remote controller
available
Yes
c. Manual setting
Item code "b0" : 0~10 setting
(*Note (3)) (*Note (4))
See Section "10-2, 10-3 or
10-4".
42
No
d. Auto airflow volume
setting
Item code "b0" : -2 setting
(*Note (4))
See Section "10-2, 10-3 or
10-4".
Auto airflow volume control
operations (*Note (5))
See Section "10-2, 10-3 or
10-4".