Schedule And Shutdown - LEGRAND CS102 User Manual

Ups snmp http agent
Hide thumbs Also See for CS102:
Table of Contents

Advertisement

Item
Temperature Hysteresis
Overload Set Point
Parameters Setting
This page allows you to set the battery replacement dates.
It's just a reminder, it has no effect on the operation of the CS102.

4.2.2. Schedule and Shutdown

Battery Test
This page let you set a schedule for Battery Auto Test. A maximum of 7 schedules can be
registered.
Description
When the temperature is very close to the set threshold, its
oscillation can generate many alarm notifications.
The hysteresis setting defines how many degrees the measured
value must change before the alarm is cleared. For example, if
the temperature limit is set to 60 °C and the hysteresis is set to 2
°C, the alarm will activate at 60 °C but will not clear until the
temperature drops below 58 °C. The default setting of the
hysteresis is 0 °C, while the setting range is 0~20 °C.
Displays the UPS output overload alarm threshold. When the
UPS output load exceeds this limit, the CS102 takes the action
specified in the "UPS Management → Schedule and Shutdown
→ Event Shutdown" page
22
CS102 SNMP Card
User Manual