"B"
REQUIRED
SPREADER
BARS
UNIT
549J*07A/D
549J*08D
549J*09D
NOTES:
1. SPREADER BARS REQUIRED — Top damage will occur if spreader bars are not used.
2. Dimensions in ( ) are in millimeters.
3. Hook rigging shackles through holes in base rail, as shown in detail "A." Holes in base rails are centered around the unit center of
gravity. Use wooden top to prevent rigging straps from damaging unit.
Step 7 — Convert to Horizontal and Connect
Ductwork (when required)
Unit is shipped in the vertical duct configuration. Unit without fac-
tory-installed economizer or return-air smoke detector option may
be field-converted to horizontal ducted configuration. To convert
to horizontal configuration, remove screws from side duct opening
covers (see Fig. 8) and remove covers. Use the screws to install
the covers on vertical duct openings with the insulation-side
down. The panels must be inserted into the notches on the basepan
to properly seal. The notches are covered by the tape used to se-
cure the insulation to the basepan and are not easily seen. See
Fig. 9 for position of the notches in the basepan. Seals around duct
openings must be tight. Secure with screws as shown in Fig. 10.
Cover seams with foil duct tape.
Field-supplied flanges should be attached to horizontal duct open-
ings and all ductwork should be secured to the flanges. Insulate
and weatherproof all external ductwork, joints, and roof or build-
ing openings with counter flashing and mastic in accordance with
applicable codes.
Do not cover or obscure visibility to the unit's informative data
plate when insulating horizontal ductwork.
36"- 54"
(914-1371)
"C"
"A"
SEE DETAIL "A"
MAX WEIGHT
LB
KG
IN.
1100
500
88.0
1315
598
88.0
1505
684
88.0
Fig. 7 — Rigging Details
PLACE ALL SEAL STRIP IN PLACE
BEFORE PLACING UNIT ON ROOF CURB.
DUCT END
DIMENSIONS
A
MM
IN.
2235
40.8
2235
41.6
2235
40.0
REMOVABLE HORIZONTAL
RETURN DUCT OPENING COVER
Fig. 8 — Horizontal Conversion Panels
Fig. 9 — Location of Notches
12
DETAIL "A"
B
C
MM
IN.
1035
41.5
1057
49.5
1015
49.5
REMOVABLE HORIZONTAL
SUPPLY DUCT OPENING COVER
NOTCHES
BASEPAN
MM
1055
1257
1257
NOTCHES