Bryant 549B Installation, Start-Up And Service Instructions Manual
Bryant 549B Installation, Start-Up And Service Instructions Manual

Bryant 549B Installation, Start-Up And Service Instructions Manual

Durapac plus series sizes 090-120 7 1/2 to 10 tons single package rooftop high-efficiency heat pump unit

Advertisement

Quick Links

IMPORTANT - READ BEFORE INSTALLING
Read and become familiar with these installation instruc-
tions before installing this unit.
Be sure the installation conforms to all applicable local and
national codes.
These instructions contain important information for the
proper maintenance and repair of this equipment. Retain
these instructions for future use.
CONTENTS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-33
I. Step 1 - Provide Unit Support. . . . . . . . . . . . . . . . . 1
II. Step 2 - Field Fabricate Ductwork . . . . . . . . . . . . . 1
External Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
IV. Step 4 - Rig and Place Unit . . . . . . . . . . . . . . . . . . . 3
VII. Step 7 - Adjust Indoor-Fan Speed . . . . . . . . . . . . 19
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34-36
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .36-39
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . . . .40-42
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance func-
tions of cleaning coils and filters and replacing filters. All
other operations should be performed by trained service per-
sonnel. When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to the
unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves.
Use quenching cloth for unbrazing operations. Have fire
extinguishers available for all brazing operations.
WARNING: Before performing service or mainte-
nance operations on unit, turn off main power switch
to unit and install lockout tag on disconnect. Electrical
shock could cause personal injury.
CAUTION: Ensure voltage listed on unit data
plate agrees with electrical supply provided for the
unit.
installation, start-up and

service instructions

SINGLE PACKAGE ROOFTOP
HIGH-EFFICIENCY HEAT PUMP UNITS
Cancels: II 549B-90-5
This unit is shipped in the vertical configuration. To convert
to horizontal configuration, remove the side duct opening
covers. Using the same screws, install the covers on the ver-
tical duct openings with the insulation-side down. Seals
around duct openings must be tight.
I. STEP 1 - PROVIDE UNIT SUPPORT
A. Roof Curb
Assemble and install the accessory roof curb in accordance
with instructions shipped with the curb. See Fig. 1. Install
Page
insulation, cant strips, roofing felt, and counter flashing as
shown. Ductwork must be attached to the curb. If electric con-
trol power will be routed through the basepan, use the
appropriate accessory kit listed in Fig. 1, available from your
local distributor. Attach the accessory thru-the-bottom ser-
vice connections to the basepan in accordance with the acces-
sory installation instructions. Connections must be installed
before the unit is set on the roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install the gasket supplied with
the roof curb as shown in Fig. 1. An improperly applied gas-
ket can also result in air leaks and poor unit performance.
The roof curb should be level. Unit leveling tolerances are
shown in Fig. 2. This is necessary for the unit drain to func-
tion properly. Refer to Accessory Roof Curb Installation
Instructions for additional information as required.
B. Slab Mount (Horizontal Units Only)
Provide a level concrete slab that extends a minimum of 6 in.
beyond the unit cabinet. Install a gravel apron in front of the
condenser coil air inlet to prevent grass and foliage from
obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
C. Alternate Unit Support (Curb or Slab Mount)
A non-combustible sleeper rail can be used in the unit curb
support area. If sleeper rails cannot be used, support the
long sides of the unit with a minimum of 3 equally spaced
4-in. x 4-in. pads on each side.
II. STEP 2 - FIELD FABRICATE DUCTWORK
On vertical discharge units, secure all ducts to the roof curb
and building structure. Do not connect ductwork to the unit.
For horizontal applications, field-supplied flanges should be
attached to horizontal discharge openings and all ductwork
attached to the flanges. Insulate and weatherproof all exter-
nal ductwork, joints, and roof openings with counter flashing
and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insu-
lated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return
should be ducted through the roof deck to comply with appli-
cable fire codes.
Dura Pac Plus Series
Sizes 090-120
1
7
/
to 10 Tons
2
II 549B-90-6
10/15/05

INSTALLATION

549B

Advertisement

Table of Contents
loading

Summary of Contents for Bryant 549B

  • Page 1: Table Of Contents

    installation, start-up and 549B Dura Pac Plus Series service instructions Sizes 090-120 SINGLE PACKAGE ROOFTOP to 10 Tons HIGH-EFFICIENCY HEAT PUMP UNITS Cancels: II 549B-90-5 II 549B-90-6 10/15/05 IMPORTANT — READ BEFORE INSTALLING INSTALLATION This unit is shipped in the vertical configuration. To convert Read and become familiar with these installation instruc- to horizontal configuration, remove the side duct opening tions before installing this unit.
  • Page 2 A minimum clearance to combustibles is not required around first 12 in. of ductwork. Cabinet return-air static pressure (a ductwork on vertical discharge units. On horizontal dis- negative condition) shall not exceed 0.30 in. wg with econo- charge units, a minimum clearance of 1 in. is required for the mizer or 0.45 in.
  • Page 3: Step 3 - Install Condensate Drain Line And External Trap

    left on the unit. Rollers may be used to move the unit across a roof. Level by using the unit frame as a reference. See Table 1 and Fig. 4 for additional information. Operating weight is shown in Table 1 and Fig. 4. Lifting holes are provided in the base rails as shown in Fig.
  • Page 4 A. Positioning Do not install the unit indoors. Do not locate the unit air inlet near exhaust vents or other sources of contaminated air. Maintain clearance around and above the unit to provide proper airflow and service access. See Fig. 5. Although the unit is weatherproof, guard against water from higher level runoff and overhangs.
  • Page 5 — —...
  • Page 6: Step 5 - Make Electrical Connections

    Institute/National Fire Protection Association), latest components. (Such operation would invalidate any applica- edition, and local electrical codes. Failure to follow this ble Bryant warranty.) warning could result in the installer being liable for personal injury of others. A. Field Power Supply All units except 208/230-v units are factory wired for the voltage shown on the nameplate.
  • Page 7 Table 3A — Electrical Data — Standard Motor Units Without Electrical Convenience Outlet MINIMUM UNIT VOLTAGE COMPRESSOR NOMINAL ELECTRIC HEAT* POWER SUPPLY DISCONNECT UNIT RANGE (each) (each) VOLTAGE SIZE† 549B (V-Ph-Hz) Min Max kW** MOCP — — 38.2/ 38.2 40/ 40†† 40/ 40 242/242 7.8/10.4...
  • Page 8 Table 3C — Electrical Data — High-Static Motor Units Without Electrical Convenience Outlet MINIMUM UNIT VOLTAGE COMPRESSOR NOMINAL ELECTRIC HEAT* POWER SUPPLY DISCONNECT UNIT RANGE (each) (each) VOLTAGE SIZE† 549B (V-Ph-Hz) Min Max kW** MOCP — — 41.3/ 41.3 45/ 45†† 44/ 44 267/267 7.8/10.4...
  • Page 9 LEGEND AND NOTES FOR TABLES 3A-3D LEGEND Example: Supply voltage is 460-3-60. — Full Load Amps AB = 452 v HACR — Heating, Air Conditioning BC = 464 v and Refrigeration AC = 455 v — Indoor Fan Motor — Locked Rotor Amps 452 + 464 + 455 Average Voltage = —...
  • Page 10: Step 6 - Adjust Factory-Installed Options

    80 amperes and cannot be used if rooftop dance with thermostat installation instructions. electrical rating exceeds 80 amperes. NOTE: If using a Bryant electronic thermostat, set the ther- B. Manual Outdoor-Air Damper mostat configuration for “non-heat pump operation.” This The outdoor-air hood and screen are attached to the basepan family of products does not require an “O”...
  • Page 11 COOL STAGE 1 Y1/W2 WIRE HEAT STAGE 1 W/W1 CONNECTIONS COOL STAGE 2 Y/Y2 LOW-VOLTAGE SECTION HEAT STAGE 2 O/W2 (CONNECTION BOARD) 24 VAC HOT 24 VAC COM IPD/X OUTDOOR AIR SENSOR THERMOSTAT DIPSWITCH SETTINGS LEGEND Field Wiring NOTE: Underlined letter indicates active thermostat output when con- figured for A/C operation.
  • Page 12 C. Optional EconoMi$er IV See Fig. 14 for EconoMi$er IV component locations. NOTE: These instructions are for installing the optional EconoMi$er IV. Refer to the accessory EconoMi$er IV instal- lation instructions when field installing an EconoMi$er IV accessory. 1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward.
  • Page 13 SIDE PANEL HOOD BOX BRACKET SIDE PANEL CAULK HERE INDOOR INDOOR COIL COIL Fig. 16 — Hood Box Removal ACCESS ACCESS PANEL PANEL 5. Remove the shipping tape holding the economizer Fig. 17 — Indoor Coil Access Panel Relocation barometric relief damper in place. 6.
  • Page 14 FOR OCCUPANCY CONTROL REPLACE JUMPER WITH FIELD-SUPPLIED TIME CLOCK Potentiometer Defaults Settings: LEGEND NOTES: Power Exhaust Middle 1. 620 ohm, 1 watt 5% resistor should be removed only when using differential DCV— Demand Controlled Ventilation Minimum Pos. Fully Closed enthalpy or dry bulb. IAQ —...
  • Page 15 Outdoor Dry Bulb Changeover 6000 The standard controller is shipped from the factory configured for outdoor dry bulb changeover control. The outdoor air and 5000 supply air temperature sensors are included as standard. For 4000 this control mode, the outdoor temperature is compared to an adjustable set point selected on the control.
  • Page 16 If a separate field-supplied transformer is used to power the IAQ sensor, the sensor must not be grounded or the EconoMi$er IV control board will be damaged. Exhaust Set Point Adjustment The exhaust set point will determine when the exhaust fan runs based on damper position (if accessory power exhaust is installed).
  • Page 17 (29) (32) (35) (38) (41) (43) CONTROL CONTROL POINT CURVE APPROX. °F (°C) AT 50% RH (27) 73 (23) 70 (21) 67 (19) 63 (17) (24) (21) (18) (16) (13) (10) HIGH LIMIT CURVE (10) (13) (16) (18) (21) (24) (27) (29) (32)
  • Page 18 Table 7. rate must be evaluated for design conditions. The maximum Use setting 1 or 2 for Bryant equipment. See Table 7. damper position must be calculated to provide the desired fresh air.
  • Page 19: Step 7 - Adjust Indoor-Fan Speed

    Table 7 — CO Sensor Standard Settings VENTILATION OPTIONAL RELAY ANALOG SETTING EQUIPMENT OUTPUT RATE CONTROL RANGE RELAY SETPOINT HYSTERESIS OUTPUT (cfm/Person) (ppm) (ppm) (ppm) 0-10V Proportional 0-2000 1000 4-20 mA Interface w/Standard 2-10V Proportional 0-2000 1000 Building Control System 7-20 mA 0-10V Exponential...
  • Page 20 To adjust belt tension: 1. Loosen the fan motor mounting plate nuts. 2. Size 090 and 102 — Slide the motor mounting plate away from the fan scroll for proper belt tension ( -in. deflection with 8 to 10 lb of force) and tighten the mounting nuts (see Fig.
  • Page 21 2. Values include losses for filters, unit casing, and wet coils. See Tables 10 and 11 for FIOP/accessory static pressure information. 3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify. 4. Interpolation is permissible. Do not extrapolate.
  • Page 22 Table 12 — Fan Performance 549B090 — Vertical Discharge Units; Standard Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW Watts Watts Watts Watts Watts 2250 0.53 0.73 0.95 1.19 1106 1.44 1342 2300 0.56 0.76 0.98 1.22 1140 1.48 1378 2400 0.61...
  • Page 23 Table 13 — Fan Performance 549B090 — Vertical Discharge Units; High-Static Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW Watts Watts Watts Watts Watts 2250 0.53 0.73 0.95 1.19 1106 1.44 1342 2300 0.56 0.76 0.98 1.22 1140 1.48 1378 2400 0.61...
  • Page 24 Table 14 — Fan Performance 549B102 — Vertical Discharge Units; Standard Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW Watts Watts Watts Watts Watts 2500 0.41 0.54 0.67 0.80 0.93 2600 0.45 0.59 0.72 0.85 0.99 2700 0.50 0.64 0.77 0.91 1.05...
  • Page 25 Table 15 — Fan Performance 549B102 — Vertical Discharge Units; High-Static Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 2500 0.41 0.54 0.67 0.80 0.93 2600 0.45 0.59 0.72 0.85 0.99 2700 0.50 0.64 0.77 0.91...
  • Page 26 Table 16 — Fan Performance 549B120 — Vertical Discharge Units; Standard Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 3000 0.65 0.80 0.95 1.11 1034 1.26 1177 3100 0.70 0.86 1.02 1.18 1100 1.34 1249 3200...
  • Page 27 Table 17 — Fan Performance 549B120 — Vertical Discharge Units; High-Static Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 3000 0.65 0.80 0.95 1.11 1034 1.26 1177 3100 0.70 0.86 1.02 1.18 1100 1.34 1249 3200...
  • Page 28 Table 18 — Fan Performance 549B090 — Horizontal Discharge Units; Standard Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 2250 0.43 0.64 0.86 1.10 1021 1.34 1252 2300 0.45 0.66 0.89 1.13 1050 1.38 1283 2400...
  • Page 29 Table 19 — Fan Performance 549B090 — Horizontal Discharge Units; High-Static Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 2250 0.43 0.64 0.86 1.10 1021 1.34 1252 2300 0.45 0.66 0.89 1.13 1050 1.38 1283 2400...
  • Page 30 Table 20 — Fan Performance 549B102 — Horizontal Discharge Units; Standard Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 2500 0.37 0.50 0.64 0.78 0.93 2600 0.41 0.54 0.68 0.83 0.98 2700 0.45 0.58 0.73 0.88...
  • Page 31 Table 21 — Fan Performance 549B102 — Horizontal Discharge Units; High-Static Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 2500 0.37 0.50 0.64 0.78 0.93 2600 0.41 0.54 0.68 0.83 0.98 2700 0.45 0.58 0.73 0.88...
  • Page 32 Table 22 — Fan Performance 549B120 — Horizontal Discharge Units; Standard Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 3000 0.58 0.73 0.88 1.05 1.22 1135 3100 0.63 0.78 0.94 1.11 1035 1.28 1196 3200 0.68...
  • Page 33 Table 23 — Fan Performance 549B130 — Horizontal Discharge Units; High-Static Motor (Belt Drive)* EXTERNAL STATIC PRESSURE (in. wg) AIRFLOW (Cfm) Watts Watts Watts Watts Watts 3000 0.58 0.73 0.88 1.05 1.22 1135 3100 0.63 0.78 0.94 1.11 1035 1.28 1196 3200 0.68...
  • Page 34: Pre-Start-Up

    PRE-START-UP d. Make sure that all tools and miscellaneous loose parts have been removed. WARNING: Failure to observe the following warn- ings could result in serious personal injury: START-UP 1. Follow recognized safety practices and wear I. UNIT PREPARATION protective goggles when checking or servicing Make sure that the unit has been installed in accordance refrigerant system.
  • Page 35 VIII. COOLING If the space temperature continues to fall while W1 is energized, W2 will be energized with 24 v, and the heater To start the unit, turn on main power supply. Set the system contactor(s) (HC) will be energized, which will energize the selector switch at COOL position and fan switch at AUTO electric heater(s).
  • Page 36: Service

    E. Defrost Clean 2-row coils as follows: When the temperature of the outdoor coil drops below 28 F as 1. Turn off the unit power and install lockout tag on sensed by the defrost thermostat (DFT2) and the defrost disconnect. timer is at the end of the timed period (adjustable at 30, 50, or 2.
  • Page 37 V. ECONOMI$ER IV ADJUSTMENT Refer to Optional EconoMi$er IV section on page 12. VI. HIGH-PRESSURE SWITCH Located on the compressor hot gas line is a high-pressure switch with a Schrader core depressor. This switch opens at 428 psig and closes at 320 psig. No adjustment is necessary. Refer to Table 1.
  • Page 38 SUCTION LINE TEMPERATURE DEG F XI. REPLACEMENT PARTS Fig. 39 — Cooling Charging Chart, 549B102 A complete list of replacement parts may be obtained from any Bryant distributor. Fig. 38 — Cooling Charging Chart, 549B090 Fig. 40 — Cooling Charging Chart, 549B120 —...
  • Page 39: Service

    LEGEND — Limit Switch — American Wire Gage Terminal Block — Contactor, Compressor — Minimum Circuit Amps — Capacitor — Outdoor-Fan Contactor Terminal Econ 2 Position Board — Outdoor-Fan Motor — Circuit Breaker — Compressor Lockout — Plug Splice COMP —...
  • Page 40: Troubleshooting

    TROUBLESHOOTING I. UNIT TROUBLESHOOTING Refer to Table 24 for troubleshooting information. Table 24 — Heating and Cooling Troubleshooting PROBLEM CAUSE REMEDY Compressor and Power failure. Call power company. Outdoor Fan Fuse blown or circuit breaker tripped. Replace fuse or reset circuit breaker. Will Not Start.
  • Page 41 (negative node). The LED for both DCV and Exhaust shown. An EconoMi$er IV simulator program is available should turn on. The actuator should drive to between from Bryant to help with EconoMi$er IV training and 90 and 95% open. troubleshooting.
  • Page 42 3. Set DCV maximum position potentiometer to previ- 7. Remove jumper from TR to N. ous setting. 8. Remove jumper from TR to 1. 4. Set minimum position, DCV set point, and exhaust 9. Remove 5.6 kilo-ohm resistor from T and T1. Recon- potentiometers to previous settings.
  • Page 43: Index

    INDEX Access panels Operating sequence Barometric flow capacity Cooling Charging chart, refrigerant Defrost Clearance EconoMi$er IV 2, 5 sensor Heating Configuration Outdoor air hood 12, 13 Settings Outdoor air temperature sensor 17, 19 Compressor Outdoor air inlet screens Lubrication Cleaning Mounting Outdoor coil Rotation...
  • Page 46 Copyright 2005 Bryant Heating & Cooling Systems Printed in U.S.A. CATALOG NO. 04-53549002-01...
  • Page 48: Start-Up Checklist

    PSIG VERIFY REFRIGERANT CHARGE USING COOLING CHARGING CHARTS ON PAGE 38. GENERAL SET ECONOMI$ER IV MINIMUM VENT AND CHANGEOVER SETTINGS TO MATCH JOB REQUIREMENTS (IF EQUIPPED) CL-1 Copyright 2005 Bryant Heating & Cooling Systems Printed in U.S.A. CATALOG NO. 04-53549002-01...

This manual is also suitable for:

Durapac plus seriesDurapac plus 549b

Table of Contents