OM-2032 / Operation and Maintenance Manual
100D20 / Generator Sets
(2) 28-V DC output cable installation
Install DC output cables as illustrated in Figure 3. Use size 4/0 size cables.
2. Preparation for Storage
When a generator set is to be stored or removed from operation, special precautions should be taken
to protect the internal and external parts from rust, corrosion, and gumming in the engine fuel system.
a. General
(1) The unit should be prepared for storage as soon as possible after being removed from service.
(2) During winter months the unit should be stored in a dry, heated building.
(3) Moisture absorbing chemicals are available for use when excessive dampness is a problem.
The unit must be completely packaged and sealed if moisture absorbing chemicals are to be
effective.
b. Temporary Storage
When storing the unit for 30 days or less, prepare as follows:
(1) Lubricate the unit completely in accordance with instructions in Sect. 2-1. This will include
changing engine oil, and all filter elements.
(2) Start the engine and operate for about two minutes so that all internal engine components will
be coated with new oil.
March 31/94 Revised
Output Terminal Panel Arrangements
Figure 2
Chapter 1-2
Page 3