ExMax
¼ turn actuators – size M
Electrical, explosion proof rotary actuators with integrated Ex-i circuit (optional)
On-off / 3-pos. control mode, 24...240 VAC/DC, 95° angle of rotation incl. 5° pretension
24 – 40 Nm with safety operation (spring return), optional with auxiliary switches
ATEX tested in acc. with directive 2014 /34/ EU for zone 1, 2, 21, 22
Compact. Easy installation. Universal. Cost effective. Safe.
Type
Torque
ExMax- 30 - F3
24 Nm
ExMax- 50 - F3
40 Nm
ExMax- 30 - SF3
24 Nm
ExMax- 50 - SF3
40 Nm
ExMax- 30 - BF3
24 Nm
ExMax- 50 - BF3
40 Nm
ExMax- ... - CTM
Types as above with aluminium housing and seawater resistant coating (cable glands brass nickel-plated)
ExMax- ... - VAM Types as above with stainless steel housing for aggressive ambient (cable glands brass nickel-plated)
*At low temperatures the spring return time might vary. For further assistance please contact our sales team.
Product views and applications
Fire /air damper
Ball valve
Description
The ExMax actuators are a revolution for safety, fire and shut-off dampers,
VAV systems, ball valves, throttle valves and other motorized applications
for HVAC systems in chemical, pharmaceutical, industrial and offshore/onshore
plants, for use in Ex-areas zone 1, 2 (gas) and zone 21, 22 (dust).
Highest protection class (ATEX) and IP67 protection, small dimensions,
only 9,5 kg weight, universal functions and an optional stainless steel
housing guarantee safe operation even under difficult environmental
conditions. High quality brushless motors guarantee long life.
All actuators are programmable and adjustable on site. Special tools or
equipment are not required. Motor running times are selectable or
adjustable on site. The integrated universal power supply is self adaptable
to input voltages in the range of 24...240 VAC/DC. The actuators are
100 % overload protected.
...Max-...-F3 actuators are equipped with spring return fail safe function.
Additionally the ...Max-...-SF3 and ...-BF3 actuators are equipped with
2 integrated, potential free auxiliary switches each and ...Max-...-BF3
comes with an intrinsically safe tripping circuit for connecting the ...Pro-TT-...
safety temperature trigger. Standard shaft connection is a double square
direct coupling with 16 × 16 mm.
Different accessories are available to adapt auxiliary switches, terminal
boxes or adaptions for ball valves and throttle valves and other armatures.
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
Supply
Motor running time
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s /90° ~ 3 s /90°
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s /90° ~ 3 s/ 90°
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s /90° ~ 3 s/ 90°
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s /90° ~ 3 s/ 90°
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s /90° ~ 3 s/ 90°
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s /90° ~ 3 s /90°
Throttle valve
Highlights
► For all types of gases, mists, vapours and dusts in zones 1, 2, 21 and 22
► Universal supply unit from 24...240 VAC/DC
►Motor running times 40–60– 90 – 120–150 s /90° adjustable on site
► On-off control with spring return function
► Ex-i circuit for direct connection of the ...Pro-TT-... safety temperature trigger
► 2 integrated auxiliary switches, switching at 5° and 85° angle of rotation
► 30 – 50 Nm actuators in the same housing size
► 100 % overload protected
► Compact design and small dimension (L × W × H ~ 288 × 149 × 116 mm)
► Direct coupling to the damper shaft with double square connection 16 × 16 mm
► 95° angle of rotation inclusive 5° pretension
► Robust aluminium housing (optional with seawater resistant coating) or in stainless steel
► IP67 protection
► Simple manual override included + preparation for comfortable manual override
► Gear made of stainless steel and sinter metal
► Weight only ~ 9,5 kg
► Integrated safety temperature sensor
► Integrated equipment for manual adjustment (push button, lamp, switch)
► Preparation for adaptable and adjustable auxiliary switches type ...Switch
www.schischek.com
Spring return* Control mode
On-off
On-off
On-off
On-off
On-off
On-off
(type ...-BF3)
E X P L O S I O N P R O O F
ExMax - ... - F3
ExMax - ... - SF3
ExMax - ... - BF3
ExMax - ... - CTM
ExMax - ... - VAM
Subject to change!
Feedback
2 × aux. switches
2 × aux. switches
2 × aux. switches + Ex-i tripping circuit SB 2.4 / 2.5 + 7.4
2 × aux. switches + Ex-i tripping circuit SB 2.4 /2.5 + 7.4
Wiring diagram
SB 2.4 / 2.5
SB 2.4 / 2.5
SB 2.4 / 2.5 + 3.2
SB 2.4 / 2.5 + 3.2
ExMax-M-F3_en
V06 – 10-Jan-2023
1 / 4

Advertisement

Table of Contents
loading

Summary of Contents for Schischek ExMax F3 Series

  • Page 1 ► Integrated equipment for manual adjustment (push button, lamp, switch) ► Preparation for adaptable and adjustable auxiliary switches type ...Switch ExMax-M-F3_en V06 – 10-Jan-2023 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 1 / 4...
  • Page 2: Special Option

    ExMax-...-S30 1.5 m cable, protective metal conduit and combination conduit glands IP67 in acc. with EN 60529 ExMax-M-F3_en V06 – 10-Jan-2023 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 2 / 4...
  • Page 3: Electrical Connection

    1000 μF 1000 μF Never use spring return actuators without external load. ExMax-M-F3_en V06 – 10-Jan-2023 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 3 / 4...
  • Page 4 They are connected by cable. ExBox- Y/S for ...Max-...-SF3 ExBox- BF for ...Max-...-BF3 ExMax-M-F3_en V06 – 10-Jan-2023 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 4 / 4...
  • Page 5 Otherwise the fuse could respond and switch off the actuator irreversibly. info-Max-M_en V01 – 26-Mar-2015 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 1 / 6...
  • Page 6 For square damper shafts 12 × 12 mm or 14 × 14 mm reducing bushes are available as optional accessories. info-Max-M_en V01 – 26-Mar-2015 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 2 / 6...
  • Page 7 Mounting to a ball valve Mounting to a butterfly valve 4 × 4 × info-Max-M_en V01 – 26-Mar-2015 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 3 / 6...
  • Page 8 B) Mount ...Switch and fix it with screws ...Max with mounted ...Switch 4 × info-Max-M_en V01 – 26-Mar-2015 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 4 / 6...
  • Page 9 24 V power supply with wire diameter 1.5 mm² = cable length 126 m electrolytic copper with a coefficient of 56 m /Ωmm²) info-Max-M_en V01 – 26-Mar-2015 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 5 / 6...
  • Page 10 ● Cable to long, voltage drop in the supply line to large ● Increase line cross section or power supply info-Max-M_en V01 – 26-Mar-2015 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 6 / 6...