Electrical Connection; Installation - Schischek ExMax F3 Series Installation Manual

Table of Contents

Advertisement

ExMax-...-F3
Special option

Electrical connection

All actuators are equipped with a universal supply unit working at a voltage range from
24...240 VAC/DC. The supply unit is self adjusting to the connected voltage!
The safety operation of the spring return function works if the supply voltage is cut or
line 3 opened. For electrical connection inside hazardous areas an Ex-e terminal box,
certificated in acc. with ATEX is required (e.g. ExBox).
An over-current protection fuse < 10 A has to be provided by installer.
Note: The initial current is appr. 2 A for 1 second.
Integrated auxiliary switches signal the rotation angle's position. U
the switches were operated with higher voltage or current.
On-off
SB 2.4
24...240 VAC/ DC
+
~
~
PE
a
1
2
3
Wiring of integrated auxiliary switches
24...240 VAC/ DC
Integrated auxiliary switches,
Grid fuse-protection recommended.
+
~
~
U < 90 V AC/DC
U > 90 V AC/DC
PE
a
1
2
3
1
On-off – spring return + Ex-i tripping circuit
24...240 VAC/ DC
Integrated auxiliary switches,
Grid fuse-protection recommended.
+
~
~
U < 90 V AC/DC
U > 90 V AC/DC
PE
a
1
2
3
4
Ex-i intrinsic safe data – for temperature trigger ExPro-TT T 1.0
U
= 5,88 V
o
I
= 24,75 mA
o
P
= 37
mW
L
o
o
C
= 0
C
i
o
L
= 0
i
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
ExMax-...-SF3
... -CTM
and I
min
min
On-off (1 wire)
24...240 VAC/ DC
+
~
~
Attention !
At 1-wire control the
electronics may re-
quire a waiting time
PE
at low temperatures
PA
1
2
3
min. max.
2 AT 10 AT
5 AT 10 AT
< 5°
> 85°
2
3
4
5
6
Ex-i tripping circuit for
ExPro-TT-... safety
min. max.
temperature trigger
2 AT 10 AT
5 AT 10 AT
< 5°
> 85°
5
6
7
8
9
1
2
IIC
IIB
IIA
50 mH
50 mH
50 mH
43 μF
1000 μF
1000 μF
www.schischek.com
ExMax-...-BF3
... -VAM
Parameters, adjustments and failure indication
Switch – Push button – Lamp
for adjustment
(behind the blanking plug)
10-position switch (S)
Push button (T)
change once
3-colour LED
Parameter selection
SB 2.5
Example:
ExMax-30-BF3
Requested parameter:
Torque
Motor running time 90 s /90°
Result:
Switch position 02
Functions, adjustments and parameters
PA
A) Self adjustment of angle of rotation
ATTENTION: To adjust the angle of rotation connect only wire 1 and 2.
Do not connect wire 3.
Apply supply voltage to wire 1 and 2. Turn switch (S) to position 02. Press
button (T) for a minimum of 3 seconds. The actuator drives to the first end posi-
SB 3.2
tion, detects the blocking position and performs a spring return to the starting posi-
tion. The LED flashes GREEN during adjustment. After that disconnect from the
mains and connect wire 3.
The adjustment takes about 93 seconds (90 sec. "On", 3 sec. "Off").
B) Selecting motor running time
Adjust parameters only if actuator is in idle state or without applied potential.
Turn switch (S) to the position required for the intended operation acc. to table
above. The selected parameters will be carried out at the actuator's next opera-
tion.
C) Function of the ExPro-TT-... in the Ex-i tripping circuit
When the ...Pro-TT's tripping circuit is opened the actuator runs into its end posi-
tion with spring return.
D) Additional information for control in On-off operation
PA
a closed
a open
The rotation direction (clockwise / counter clockwise) depends on left / right
mounting of the actuator to the damper.
SB 7.4

Installation

Ex area –
zone 1, 2, 21, 22
ExPro-TT
°C
Test
button
PA
During commissioning apply a self adjustment drive.
Never use spring return actuators without external load.
E X P L O S I O N P R O O F
Type
Torques (motor)
ExMax- 30 -...F3 ►
30 Nm
ExMax- 50 -...F3 ►
50 Nm
30 Nm
Running times
Position of switch (S)
40 s /90°
00
60 s / 90°
01
90 s / 90°
02
120 s / 90°
03
150 s / 90°
04
= actuator opens
= spring return
Auxiliary switches *
Supply *
24...240 VAC/DC ± 10 %
ExBox
Attention
Regard duty cycle at motor running times !
S
T
05
06
07
08
09
Safe area
see Technical data
* electrical wiring see diagrams
ExMax-M-F3_en
V06 – 10-Jan-2023
3 / 4