Download Print this page
Hide thumbs Also See for ExMax CTM Series:

Advertisement

Quick Links

ExMax
¼ turn actuators – size M
Electrical, explosion proof rotary actuators
3-pos. / 0...10 VDC / 4...20 mA control mode, with feedback, 24...240 VAC/DC, 95° angle of rotation
50/75 Nm, 100 Nm without and 30 Nm, 50 Nm with safety operation (spring return)
ATEX tested in acc. with directive 2014/34/ EU for zone 1, 2, 21, 22
Compact. Easy installation. Universal. Cost effective. Safe.
Type
Torque
ExMax- 50.75 - Y
50 / 75 Nm
ExMax-100 - Y
100 Nm
ExMax- 30 - YF
30 Nm
ExMax- 50 - YF
50 Nm
ExMax- ... - CTM
Types as above with aluminium housing and seawater resistant coating (cable glands brass nickel-plated)
Product views and applications
Safety damper
Ball valve
Description
The ExMax actuators are a revolution for safety, control and shut-off
dampers, VAV systems, ball valves, throttle valves and other motorized
applications for HVAC systems in chemical, pharmaceutical, industrial
and offshore/onshore plants, for use in Ex-areas zone 1, 2 (gas) and
zone 21, 22 (dust).
Highest protection class (ATEX) and IP66 protection, small dimensions,
only 9,5 kg weight, universal functions and technical data, an integrated
heater and an optional stainless steel housing guarantee safe operation
even under difficult environmental conditions. High quality brushless
motors guarantee long life.
All actuators are programmable and adjustable on site. Special tools or
equipment are not required. Motor running times and torques as well as
spring return times, according to the actuator type, are selectable or
adjustable on site. The integrated universal power supply is self adaptable
to input voltages in the range of 24...240 VAC/DC. Furthermore it is
possible to perform control signal inverting and compulsion control by
certain connections. The actuators are 100 % overload protected.
...Max-...-YF actuators are equipped with spring return fail safe function.
Standard shaft connection is a double square direct coupling with
16 × 16 mm.
Different accessories are available to adapt auxiliary switches, terminal
boxes or adaptions for ball valves and throttle valves and other armatures.
Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
Supply
Motor running time
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s/90°
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s/90°
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s/90°
24...240 VAC/DC
40 / 60 / 90 / 120 / 150 s/90°
Throttle valve
Highlights
► For all types of gas, mists, vapours and dust for use in zone 1, 2, 21 and 22
► Universal supply unit from 24...240 VAC/DC
►5 different motor running times 40 –60–90 – 120 –150 s /90°, adjustable on site
► 2 different spring return running times ~ 20 s /90°, selectable on site
► 3-pos. and 0...10 VDC, 4...20 mA control mode with or without spring return function
► Feedback signals 0...10 VDC and 4...20 mA
► Reverse function
► 30 – 50– 75–100 Nm actuators in the same housing size
► 100 % overload protected
► Compact design and small dimension (L × W × H = 288 × 149 × 116 mm)
► Direct coupling to the damper shaft with double square connection 16 × 16 mm
► 95° angle of rotation inclusive 5° pretension
► Robust aluminium housing (optional with seawater resistant coating)
► IP66 protection
► Simple manual override included + preparation for comfortable manual override
► Gear made of stainless steel and sinter metal
► Weight only ~ 9,5 kg
► Integral heater for ambient temperatures down to −40 °C
► Integral safety temperature sensor
► Integral equipment for manual adjustment (push button, lamp, switch)
► Preparation for adaptable and adjustable auxiliary switches type ...Switch
► Wide range of accessories
www.schischek.com
E X P L O S I O N P R O O F
Spring return
Control mode
3-pos., 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA
3-pos., 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA
~ 20 s/90°
3-pos., 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA
~ 20 s/90°
3-pos., 0...10 VDC, 4...20 mA 0...10 VDC, 4...20 mA
ExMax - ... - Y
ExMax - ... - YF
ExMax - ... - CTM
Subject to change!
Feedback
Wiring diagram
SB 4.0 + 4.1
SB 4.0 + 4.1
SB 4.0 + 4.1
SB 4.0 + 4.1
ExMax-M-Y_en
V01 – 20-Apr-2016
1 / 4

Advertisement

loading

Summary of Contents for Schischek ExMax CTM Series

  • Page 1 ► Preparation for adaptable and adjustable auxiliary switches type ...Switch ► Wide range of accessories ExMax-M-Y_en V01 – 20-Apr-2016 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 1 / 4...
  • Page 2 IP66 in acc. with EN 60529 Adaptions for dampers and valves on request ExMax-M-Y_en V01 – 20-Apr-2016 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 2 / 4...
  • Page 3 Regard duty cycle at motor running times ! Never use spring return actuators without external load. ExMax-M-Y_en V01 – 20-Apr-2016 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 3 / 4...
  • Page 4 ...Max-...-Y and ...-YF with integral by the included cable tail. auxiliary switches ExMax-M-Y_en V01 – 20-Apr-2016 Schischek GmbH Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 4 / 4...

This manual is also suitable for:

Exmax-50.75-yExmax-100-yExmax-30-yfExmax-50-yf