Download Print this page
Schischek ExReg-V CT Series Manual

Schischek ExReg-V CT Series Manual

Volume flow controller

Advertisement

Quick Links

ExReg-V
Volume flow controller 0...300 Pa
Electrical, explosion-proof volume flow controller (CAV / VAV)
in conjunction with ExMax-...-CY... actuators only
24 VAC /DC supply, adaptive PID controller, alarm contact
EC type-approved in acc. with ATEX directive 2014 /34 /EU for zone 1, 2, 21, 22
Compact. Easy installation. Universal. Cost effective. Safe.
Type
Sensor
ExReg- V-300
Diff. pressure
ExReg- V-300 - A
Diff. pressure
ExReg- V-300 - B
Diff. pressure
ExReg- V- ... - CT Types as above with aluminium housing and seawater resistant coating (cable glands M16 brass nickel-plated, screws in stainless steel)
ExReg- V- ... - OCT Types as above, offshore version with aluminium housing and seawater resistant coating (stainless steel tubes for clamping ring connection,
cable glands M20 brass nickel-plated, screws in stainless steel)
ExReg- V- ... - VA Types as above with stainless steel housing for aggressive ambient (cable glands M20 brass nickel-plated, screws in stainless steel)
ExReg- V- ... - OVA Types as above, offshore version with stainless steel housing for aggressive ambient (tubes for clamping ring connection and screws in stainless steel,
cable glands M20 brass nickel-plated)
Product views and applications
Volume flow controller
...Reg-V...-CT
Description
The ExReg-V... flow controller is an indispensable integrant in Building
Management Control Equipment for Chemical, Pharmaceutical, Industrial
and Offshore plants for use in hazardous areas of zones 1, 2 (gas) and
21, 22 (dust).
Highest protection class (ATEX) and IP66 protection, small dimensions,
universal functions and technical data as well as an optional stainless
steel housing guarantee safe operation even in harsh environments.
ExReg-V... is used directly in hazardous areas for control of air flows in
ventilation systems. To complete the technical solution an additional
damper actuator type ExMax-...-CY or ExMax-...-CYF (with Fail Safe
spring return) is required and also a ventilation damper with orifice plate
and a known shield factor (called k-factor).
All controllers are programmable on site with menu guide. The internal
PID control structure is simple to use and automatically configured for
standard applications. The display shows the current status during
operation for the actual value, setpoint and actuator position (can be
disabled if required).
...Reg-V...-OCT and ...-OVA offshore versions are equipped with stain-
less steel tubing Ø 6 mm.
ExMax-...-CY... – see additional data sheet
Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com
Supply
Range
Connection / Interface (analogue)
24 VAC/ DC
0...300 Pa
1 × actuator, 1 × set point
24 VAC/ DC
0...300 Pa
1 × actuator, 1 × set point, 1 × actual value, 1 × position actuator Relay contact 30 V / 0.1 A
24 VAC/DC
0...300 Pa
1 × actuator, RS485 communication
...Reg-V...-VA
Highlights
► For all type of gas, mists, vapours and dust for use in zone 1, 2, 21 and 22
► Power supply 24 VAC/DC
► Sensor and controller in one housing
► Direct connection of actuator to the controller's integrated Ex-e terminal box
► No addional Ex-i module in panel required
► No intrinsically safe wiring/ installation between sensor and panel required
► No intrinsically safe wiring/installation and no space in the panel required
► Relay output with adjustable alarm monitoring
► Scalable analogue input and output (selectable für setpoint, actual value, et al.)
► Optional analogue output for controller feedback
► Adjustable k-factor, universially applicable for any dampers
►Display with backlight, can be switched off
► Password locking
► Down to −20 °C ambient temperature applicable
► Compact design and small dimension
► Robust aluminium housing (optional with seawater resistant coating) or in stainless steel
► IP66 protection
► Offshore versions with pressure tube connection for clamping ring Ø 6 mm
www.schischek.com
E X P L O S I O N P R O O F
ExReg - V-...
ExReg - V-... - A
ExReg - V-... - B
ExReg - V- ... - CT
ExReg - V- ... - OCT
ExReg - V- ... - VA
ExReg - V- ... - OVA
Alarm contact
Relay contact 30 V / 0.1 A
Relay contact 30 V / 0.1 A
Offshore ...-OVA
ExReg-V + ExMax-...-CY
Subject to change!
Wiring diagram
SB 1.0
SB 1.1
SB 1.2
ExReg-V_en
V02 – 23-Sep-2016
1 / 8

Advertisement

loading

Summary of Contents for Schischek ExReg-V CT Series

  • Page 1 ► Offshore versions with pressure tube connection for clamping ring Ø 6 mm ExMax-...-CY... – see additional data sheet ExReg-V_en V02 – 23-Sep-2016 Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 1 / 8...
  • Page 2: Technical Data

    Kit-PTC-CBR 2 connecting tubes for tube fittings Ø 6 mm, stainless steel 316 L ExReg-V_en V02 – 23-Sep-2016 Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 2 / 8...
  • Page 3: Special Options

    ▪ Each device works automatically as a repeater Galvanic Isolation 1,5 kV ExReg-V_en V02 – 23-Sep-2016 Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 3 / 8...
  • Page 4: Installation

    For more information see data sheet of the actuator. ExMax-...-CY... – see additional data sheet ExReg-V_en V02 – 23-Sep-2016 Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 4 / 8...
  • Page 5 6.2: Status Indication actual value in m³ / h 100 m³/ h ExReg-V_en V02 – 23-Sep-2016 Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 5 / 8...
  • Page 6 Test output value terminal 11 10.0 V Set 0 ... 10 V ExReg-V_en V02 – 23-Sep-2016 Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 6 / 8...
  • Page 7 Menu 15 Leave menu 15: Leave menu Leave menu and save Back, yes ExReg-V_en V02 – 23-Sep-2016 Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 7 / 8...
  • Page 8 Ø 4,5 Stainless steel housing ...Reg-V...-OVA Ø 4.5 ~ 61 81.3 126.3 ExReg-V_en V02 – 23-Sep-2016 Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail info-de@schischek.com www.schischek.com 8 / 8...

This manual is also suitable for:

Exreg-v seriesExreg-v oct seriesExreg-v va seriesExreg-v ova seriesExreg-v-300Exreg-v-300-a ... Show all