ExMax – ¼ turn actuator
Electrical, explosion proof rotary actuators size M
On-off / 3-pos , 24...240 VAC/DC, 95° Angle of rotation incl. 5° pretention
50 - 150 Nm without and 30 Nm - 60 Nm with safety operation (spring return)
PTB-tested in acc. with ATEX RL 94/9/EC for zone 1, 2, 21, 22.
Compact. Easy installation. Universal. Cost effective. Safe.
Type
Torque
ExMax- 50.75
50 Nm & 75 Nm 24..240 VAC/DC 40/60/90/120/150 sec. at 90°
ExMax- 100
100 Nm
ExMax- 150
150 Nm
ExMax- 30 - F
30 Nm
ExMax- 50 - F
50 Nm
ExMax- 60 - F
60 Nm
ExMax- ... - S/SF Type as above but with 2 integral, potential free aux. switches, switching at 5° and 85° Angle of rotation max.24 V/1 A, 240 V/0,25 A
ExMax- ... - CTM Type as above but with aluminium housing and Amercoat paint, gearbox parts in stainless steel, cable gland and hollow rivet nickel-plated
Application
Damper
Ball valve
Description size M
The ExMax actuators are a revolution for safety, control and shut-off
dampers, ball valves, throttle valves and other motorized applications
for HVAC systems, in chemical, pharmaceutical, industrial and Offshore-
/Onshore plants, for use in Ex-areas zone 1, 2 (gas) and zone 21, 22
(dust).
Highest protection class (ATEX) and IP 66 protection, small dimensions,
only 9,5 kg weight, universal functions and technical data, an integrated
heater guarantee safe operation even under difficult environmental
conditions. High quality brushless motors guarantee long life.
All actuators are programmable and adjustable on site. Special tools or
equipment are not required. Motor running times and torques - according
to the actuator type - selectable or adjustable on site. The integrated
universal power supply is self adaptable to input voltages in the range
of 24 to 240 VAC/DC.
The actuators are 100% overload protected.
ExMax-...-F actuators are equipped with spring return fail safe function
Standard shaft connection is a double squared direct coupling with
16 × 16 mm.
Different accessories are available to adapt aux. switches, terminal boxes
or adaptations for ball valves and throttle valves.
Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com
Supply
Motor running time
24..240 VAC/DC 40/60/90/120/150 sec. at 90°
24..240 VAC/DC 40/60/90/120/150 sec. at 90°
24..240 VAC/DC 40/60/90/120/150 sec. at 90°
24..240 VAC/DC 40/60/90/120/120 sec. at 90°
24..240 VAC/DC 40/60/90/120/120 sec. at 90°
Throttle valve
Highlights
 For all type of gas, mixtures, vapours and dust for use in zone 1, 2, 21 and 22
 Universal supply unit from 24 to 240 VAC/DC
 5 different motor running times (40-60-90-120-150 sec./90°), adjustable on site
 2 different spring return running times (20 sec./90°), selectable on site
 On-off and 3-pos control with or without spring return function
 30 - 150 Nm actuators in the same size (M)
 100 % overload protected
 Compact design and small dimension (L × W × H = 286 × 150 × 116 mm)
 Direct coupling to the damper shaft with double-squared connection 16 × 16 mm
 95° Angle of rotation incl. 5° pre-tention
 Robust aluminium housing (optional Amercoat painting)
 IP66 protection
 Simple manual override include + preparation for comfortable manual override
 Gear made of stainless steel and sinter metal
 Only 9,5 kg weight
 Integral heater for ambient temperatures down to -40°C
 Integral safety temperature sensor
 Integral equipment for manual adjustment (push button, lamp, switch)
 Preparation for adaptable aux. switches type ExSwitch
 Range of accessories
www.schischek.com
E X P L O S I O N P R O O F
Spring return
Control mode
without
On-off, 3-pos
without
On-off, 3-pos
without
On-off, 3-pos
20 sec. at 90°
On-off, 3-pos
20 sec. at 90°
On-off, 3-pos
20 sec. at 90°
On-off, 3-pos
ExMax - 50.75
ExMax - 100
ExMax - 150
ExMax - 30 - F
ExMax - 50 - F
ExMax - 60 - F
ExMax - ... - S/SF
ExMax - ... - CTM
Subject to change!
Feedback Wiring diagram
-
SB 1.0
-
SB 1.0
-
SB 1.0
-
SB 1.1
-
SB 1.1
-
SB 1.1
SB 3.5

Advertisement

loading

Summary of Contents for Schischek ExMax Series

  • Page 1  Integral equipment for manual adjustment (push button, lamp, switch)  Preparation for adaptable aux. switches type ExSwitch  Range of accessories Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com www.schischek.com...
  • Page 2 Adaptations various adaptations for dampers/ valves on request IP-Protection IP 66, in acc. with EN 60529 Potential compensation external PA-terminal, 4 mm² Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com www.schischek.com...
  • Page 3 Wiring of the actuator in acc. with Additional wiring of the integral aux. switches actuator type, see wiring diagrams 1.0/1 .1 Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com www.schischek.com...
  • Page 4: E X P L O S I O N P R O O F

    Extra information „ME-M“ (see additional data sheet) extra technical information, dimensions, installation instruction and illustration D.EM-01.03-M-en-3P 24-may-2011 Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com www.schischek.com...
  • Page 5 Lengthof cable L = 126 m Cross section of A = 1,5 mm² 56m/Wmm²) Example: 24 V power supply with wire diameter 1,5 mm² = 126 m Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com...
  • Page 6 830 nF 3,7µF 4,5 µF be closed otherwise the actuator is unable to work ! 2 mH 5 mH 10 mH Push button heater Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com...
  • Page 7 / blockade position. Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com...
  • Page 8 Cable to long, voltage drop in the supply line to large l Increase line cross section or increase tension Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com...
  • Page 9: Outdoor Installation

    Otherwise the limiters could respond and switch of the actuator irreversibly. Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com www.schischek.com...
  • Page 10 „HV-M“ manual override. External applied force to the shaft can lead to mechanical damage of the actuator. Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com www.schischek.com...
  • Page 11 „HV-M“ manual override. External applied force to the shaft can lead to mechanical damage of the actuator. Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com www.schischek.com...
  • Page 12 2. ExMax, RedMax, InMax with mounted ..Switch InSwitch and fix it with 4 screws 4 × M.MZ-01.02-M-en-extra-info ME 01-jun-2011 Schischek GmbH Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn, Tel. +49 (0)9101 9081-0, Fax +49 (0)9101 9081-77, E-Mail info-de@schischek.com www.schischek.com...