Vitocrossal 300, CA3B Series 2.5 to 6.0 Technical Data

Disconnecting the Burner Assembly

1.
Disconnect the burner gas line.
Note: Do not lose gasket.
2.
Disconnect plugs 145, 41, 53 and 40 on the
burner control unit.
3.
Remove sensors 15A/B and 3A/B from the sensor
wells.
4.
Disconnect wiring and remove electrode block.
5.
Remove the 6 nuts around the burner mounting
plate.
6.
Remove upper burner section.
Note: Repeat the steps listed above for all remaining
burners installed on the boiler.