Securing The Burner To The Boiler - Riello 896 T Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

Installation
4
4.5

Securing the burner to the boiler

Introduction
The burnerRS 64/E MZ is suitable both for boilers with inverted
flame* (the long head model is advised in this case), as well as for
boilers with combustion chamber with runoff from the base (three
circulations of smoke) on which the best NO
are obtained.
The maximum thickness of the front hatch of the boiler (see position
"a", Fig. 10), complete with refractory, must not exceed 200 mm.
D8148
4
Preparing the boiler
Boring the boiler plate
Make holes in the plate shutting off the combustion chamber, as
illustrated in Fig. 12. The position of the threaded holes can be
marked using the thermal insulation screen supplied with the
burner.
D455
mm
A
RS 64/E MZ
185
275 - 325
Length of the blast tube
The length of the blast tube must be selected according to the
indications provided by the manufacturer of the boiler, and in
any case it must be greater than the thickness of the boiler door
complete with its refractory. The lengths L available are:
Blast tube 10)
• short
250 mm
• long
385 mm
20022445
low emission results
x
2
1
3
Fig. 11
Fig. 12
B
C
M 12
a
D1079
The standard equipment motor protection 1), must
be fixed on the bracket 2) using the appropriate
screws 3) with nut and washer before fitting the
casing.
WARNING
Fix the bracket to the front shield of the burner with
screw 4). See Fig. 11.
14
2
1
3
4
D8149
For boilers with front flue passes 13), a protection in refractory
material 11) must be inserted between the boiler refractory 12)
and the blast tube 10). This protection must not compromise the
extraction of the blast tube. See Fig. 13.
For boilers with a water-cooled frontal, a refractory lining is not
necessary 11)-12) unless expressly requested by the boiler
manufacturer.
13
GB
13
15
13
5
9
Fig. 13
Fig. 10
12
11
10
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rs 64/e mz

Table of Contents