Technical Data; Electrical Data; Packaging - Riello 896 T Installation, Use And Maintenance Instructions

Forced draught gas burners
Table of Contents

Advertisement

Technical description of the burner
3
3.4

Technical data

Model
Type
Output
(1)
Fuel
Gas pressure at max. output
Operation
Standard applications
Room temperature
Combustion air temperature
Noise level
(3)
Reference conditions: Room temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m above sea level.
(1)
Pressure on the pressure switch socket Fig. 27 with zero pressure in the combustion chamber and at maximum burner output.
(2)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum output.
(3)
3.5

Electrical data

Motor IE1
Model
Electrical supply
Fan motor (rating)
Operating current
Acceleration current
Ignition transformer
Absorbed electrical power
Protection level
Motor IE2
Model
Electrical supply
Fan motor (rating)
Operating current
Acceleration current
Ignition transformer
Absorbed electrical power
Protection level
3.6

Packaging

The burners are delivered in cardboard packaging with overall dimensions as in the
table.
The weight of the burner complete with its packaging is shown in table.
mm
A
RS 64/E MZ
1200
(1) Blast tube: short-long
20022445
maximum
minimum
- Gas: G20/G25
(2)
B
C
520
580
kW
Mcal/h
kW
Mcal/h
Natural gas: G20 (methane gas) - G21 - G22 - G23 - G25
mbar
Intermittent (min. 1 stop in 24 hours)
Two progressive or modulating stages with kit (see ACCESSORIES).
Boilers: water, steam, diathermic oil
°C
0 - 40
°C max
60
dB(A)
230V - 400V with neutral ~+/-10% 50 Hz - three-phase
rpm
V
W
A
A
V1 - V2
I1 - I2
W max
IP 40
230V - 400V with neutral ~+/-10% 50 Hz - three-phase
rpm
V
W
A
A
V1 - V2
I1 - I2
W max
IP 40
kg
(1)
42 - 44
7
GB
RS 64/E MZ
896 T
400 - 850
345 - 730
150
130
10.7 / 16.1
76
RS 64/E MZ
2810
230 / 400
1100
4.7 - 2.7
22 - 13
230 V - 1 x 15 kV
1 VA - 25 mA
1500
RS 64/E MZ
2850
230 / 400
1100
4 - 2.3
33 - 19
230 V - 1 x 15 kV
1 VA - 25 mA
1500
D88
Fig. 1

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rs 64/e mz