Installation Instructions - Panasonic CS/CU-HU12ZKY Series Operating & Installation Instructions Manual

Table of Contents

Advertisement

Installation instructions

Select the Best Location
Indoor Unit
Do not install the unit in excessive oil fume area such
as kitchen, workshop and etc.
There should not be any heat source or steam near
the unit.
There should not be any obstacles blocking the air
circulation.
A place where air circulation in the room is good.
A place where drainage can be easily done.
A place where noise prevention is taken into
consideration.
Do not install the unit near the door way.
Ensure the spaces indicated by arrows from the wall,
ceiling, fence or other obstacles.
Recommended installation height for indoor unit
shall be at least 2.5 m.
Attached accessories
No.
Accessories part
Installation plate
Installation plate fixing
screw
Remote Control
Battery
Remote control holder
fixing screw
Remote control holder
* Applicable for selected models only.
16
Applicable piping kit
CZ-3F5, 7EN
CZ-4F5, 7, 10BP
CZ-52F5, 7, 10B
Outdoor Unit
If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from
the condenser is not obstructed.
There should not be any animal or plant which could
be affected by hot air discharged.
Keep the spaces indicated by arrows from wall,
ceiling, fence or other obstacles.
Do not place any obstacles which may cause a short
circuit of the discharged air.
If piping length is more than 7.5m, additional
refrigerant should be added as shown in the Table A.
Qty.
No.
*Piping kit
1
5
*Connection cable
1
**Do not use as
Power Supply
2
Cord
*Ag Clean Filter
2
*PM 0.1 Filter
1
*Band
Piping size
Gas
9.52 mm (3/8")
12.7 mm (1/2")
15.88 mm (5/8")
Accessories part
Liquid
6.35 mm (1/4")
6.35 mm (1/4")
6.35 mm (1/4")
Qty.
1 Set
1
1
1
4