I/O Wiring
6-5-2 Output Wiring
Wire the analog output as shown in the following illustration. Use shielded
twisted-pair cables to connect field devices.
The 4 to 20-mA current output is always output even when a voltage output (0 to
10 V or –10 to 10 V) has been set.
When using both the current and voltage outputs, the total output current must
be 21 mA or less.
Voltage Output
Analog I/O Unit
0 V
Current Output
Analog I/O Unit
0 V
Shielded twisted-
pair cable
Shielded twisted-
pair cable
Section
6-5
Voltage
input
device
Current
input
device
111