Unigas C83X Installation Manual page 32

Hide thumbs Also See for C83X:
Table of Contents

Advertisement

PART III: OPERATION
Gas valveversion with SKP2 (built-in pressure stabilizer)
To increase or decrease gas pressure, and therefore gas flow rate, remove the cap T and use
a screwdriver to adjust the regulating screw VR. Turn clockwise to increase the flow rate,
counterclockwise to reduce it.
MultiBloc MBE Regulation VD-R whith PS
Decreasing pressure
Fig. 7
ATTENTION: To set the outlet pressure of the VD-R regulator, act on the adjustment ring nut (Fig. 10)
The position of the indicator in the dial indicates the value of the outlet pressure calculated as a percentage of the
full scale of the PS sensor (Fig. 11)
Outlet
MIN
10%
pressure
4 mbar
10 mbar
PS-10/40
0,4 kPa
1,0 kPa
2 "w.c.
4 "w.c.
20 mbar
50 mbar
PS-50/200
2,0 kPa
5,0 kPa
8 "w.c.
20 "w.c.
Increasing pressure
25%
50%
75%
25 mbar
50 mbar
75 mbar
2,5 kPa
5,0 kPa
7,5 kPa
10 "w.c.
20 "w.c.
30 "w.c.
125 mbar
250 mbar
375 mbar
12,5 kPa
25,0 kPa
37,5 kPa
50 "w.c.
100 "w.c.
150 "w.c.
Setting scale is „Not" linear! Various sensors available.
Output pressure according to sensor's measuring
range.
Adjust the outlet pressure to the value specified by the
burner or equipment manufacturer!
While making outlet pressure adjustments, do not
exceed a value that creates a hazardous condition to the
burner!
MAX
100 mbar
10,0 kPa
40 "w.c.
500 mbar
50,0 kPa
Fig. 8
200 "w.c.
Adjusting output pressure for positive pressure
systems (requires PS-10/40 or PS-50/200):
32
T
25%
50%
10%
Min.
VR
+
-
75%
Max.

Advertisement

Table of Contents
loading

Table of Contents