BURNERS WITH INVERTER VARIANT (if provided)
LMV2x/3x
M-.MD.x.xx.x.x.xx.EB
MG.MD.x.xx.x.x.xx.EC
The LMV37.400/LMV26.300 electronic cam burners with fan motor driven by inverter in addition to the air and fuel adjustment curves
also have a speed adjustment curve of the fan motor.
The LMV equipment through a sensor controls the fan motor revolutions and with a signal in 0÷10V controls it through the inverter.
Generally the curve of the inverter goes from 50% to 100% of the engine revolutions. This, in addition to improving the setting of the
burner also allows a saving on the consumption of the fan engine.
Two series of interchangeable Inverters
version with Inverter FC101 and FC102
Terminal interface with Inverter
Braking resistances
possibility of use only for FC102
Danfoss FC102
with protective grid
Sealed
19
PART II: INSTALLATION
Danfoss FC101