Auxiliary Relay 1 And 2 - Chamberlain LiftMaster CSW200101U Installation Manual

Commercial high-traffic ac swing gate operator
Table of Contents

Advertisement

Normally Open (N.O.) and Normally Closed (N.C.) relay contacts to control external devices, for connection of Class 2, low voltage (42 Vdc [34 Vac] max 5
Amps) power sources only. Function of relay contact activation determined by switch settings.
RELAY SETTING
SWITCH SETTINGS
1
OFF
Off (no feature
selected)
OFF
Open Limit Switch
OFF
Close Limit Switch
OFF
Gate Motion
ON
Pre-Motion Delay
ON
Power
ON
Tamper
ON
Cycle Quantity
Feedback*
CYCLE COUNT
* First, note the current Aux Relay switch positions. To determine
the actual cycles that the gate operator has run (in thousands),
set all three Aux Relay switches to the ON setting for Aux Relay
1. The Expansion Board's 1, 2, and 3 LEDs will blink out the
cycle count, with 1 LED blinking 1000's, 2 LED blinking
10,000's, 3 LED blinking 100,000's, and simultaneously all
three LED's blink 1,000,000's (e.g. 1 LED blinks 3 times, 2 LED
blinks 6 times, and 3 LED blinks once. Cycle count is 163,000.).
Cycle count displayed is between 1,000 and 9,999,000 cycles.
After servicing, set Aux Relay switches back to their appropriate
positions. Cycle count cannot be reset or changed. If under
1,000 cycles the 1, 2, and 3 LEDs will turn on for 10 seconds,
then turn off.
NOTE: The expansion board will flash the cycle count 3 times
then all the LEDs will turn on solid for 10 seconds then turn off.
AUXILIARY RELAY WIRING EXAMPLE
SHADOW INTERUPT
SHADOW INTERRUPT
EXIT
EXIT
AUX RELAY 1
EXPANSION BOARD OVERVIEW

AUXILIARY RELAY 1 AND 2

2
3
OFF
OFF
Relay always off.
OFF
ON
Energizes at open limit. Use with SAMS (Sequenced Access Management System, jointly with barrier
gate).
ON
OFF
Energizes when not at close limit. For an additional audible or visual display, connect an external light
(low voltage).
ON
ON
Energizes when motor is on (gate in motion). For an additional audible or visual display, connect an
external buzzer or light (low voltage).
OFF
OFF
Energizes 3 seconds before gate motion and remains
energized during gate motion. The onboard alarm will
sound. For an additional audible or visual display,
connect an external buzzer or light (low voltage).
ON
OFF
OFF
ON
Energizes if gate is manually tampered with by being pushed off of close limit. For an additional audible
or visual display, connect an external buzzer or light (low voltage).
ON
ON
The 1, 2, and 3 LEDs will blink out the cycle count
(cycle count is stored on the control board). See
below.
SBC
OPN
CLS
STP
COM
AUX RELAY 2
AUX RELAY 1
Not used.
RED/GREEN LIGHT FUNCTIONALITY
Red light
wired to AUX RELAY 1.
GATE STATE
Closed
Opening
Open
Closing
Defined Mid Stop
Undefined Mid
Stop
Timer more than 5
seconds
Timer less than 5
seconds
* For red light ON when gate is closed, set switch 1 on AUX RELAY 1 to ON
32
AUX RELAY 2
Energizes 3 seconds before gate motion and
remains energized during gate motion. For an
additional audible or visual display, connect an
external buzzer or light (low voltage).
Red/green light functionality, see below.
Green light
wired to AUX RELAY 2.
AUX RELAY 1 SWITCHES
AUX RELAY 2 SWITCHES
1 OFF
2 OFF
3 OFF
1 ON
Red light OFF*
Red light ON/Flash
Red light OFF
Red light ON/Flash
n/a
Red light ON
Red light OFF
Red light ON/Flash
Traffic Light
Class 2 Power Source
(42 Vdc [34 Vac], 5 A maximum)
+
2 ON
3 ON
Green light OFF
Green light OFF
Green light ON
Green light OFF
n/a
Green light OFF
Green light ON
Green light OFF