Navien NPE-180A2 Installation Manual page 78

Npe condensing water heaters
Hide thumbs Also See for NPE-180A2:
Table of Contents

Advertisement

H
W
End Cap
Unit
Unit
1
2
Siphon Loop Drain Hose
Drain
Common Vent Length Table
[Total Length (L) = W + H]
Vent Length for NPE Water Heater Units
Required
Model
Load
(Total
NPE-240A2/S2 D=3" D=4" D=6" D=8"
BTU/H)
399,800
2
599,700
3
799,600
4
999,500
5
1,199,400
6
1,399,300
7
1,599,200
8
1,799,100
9
1,999,000
10
2,198,900
11
2,398,800
12
Every 90° elbow used is equivalent to
Note
8 linear feet (2.4 m) of vent length.
The maximum equivalent length of
the branch pipe from the unit to the
common vent trunk is 16 equivalent feet.
Branch pipe lengths are not added
to the allowable equivalent vent
lengths that are provided in the
following charts.
78
Installing a Common Vent System
Exhaust
D
Unit
Intake
12
Total Length (ft)
60
106
200
40
71
160
30
53
120
42
96
150
35
80
142
30
68
121
60
106
53
94
48
85
43
77
40
71
Example of a Typical Installation
(Direct & Non-Direct Vent)
The following illustration depicts an example of a
common vent system installed for a cascade system
of 12 Navien NPE heater units.
Unit 1 Unit 2
Unit 12
Unit 1 Unit 2
Unit 12
[Direct Vent]
Maximum
length 20'
(6 m)
Minimum
length 36"
(91 cm)