Navien NPE-180A2 Installation Manual page 56

Npe condensing water heaters
Hide thumbs Also See for NPE-180A2:
Table of Contents

Advertisement

Two-pipe Vertical Venting - Intake and exhaust
pipes do not have to terminate in the same area.
36" (900 mm) min.
Intake Air
Non-Concentric Sidewall Venting: Air is drawn
from a different location that is at least 12 in. (300
mm) away from the exhaust termination. The
exhaust termination can be located either on the
sidewall or roof. Try to minimize the length of the
intake air pipe when installing the vent.
*12" (300 mm) above the highest anticipated snow
level, or as required by local codes, whichever is
greater.
56
Installing the Water Heater
Exhaust Gas
12" (300 mm) min
From any
obstruction
(above, below,
left, or right)
Concentric Sidewall Venting
Combustion Air Intake
Exhaust
Gas
Maintain 12" (300mm) min. clearance
above highest anticipated snow level or
Concentric Vertical Venting
Exhaust Gas
Combustion
Air Intake
For cascade applications, the required
Note
horizontal clearance between
terminations is 12" for both sidewall
and vertical venting installations.
CAUTION
Do not vertically stack concentric
terminations on sidewalls. The
circulation of exhaust gases will
cause improper operation of the
water heater.
Combustion
Air Intake
Exhaust
Gas
1 in. (25 mm) min.
grade, whichever is greater.
Maintain 12" (300 mm)
min. clearance above
highest anticipated
snow level or grade,
whichever is greater
(maximum of 24"
above roof).