c. Fully open a hot water fixture and set the
water heater to operate at 1-stage MIN
mode (refer to "Setting the Operation Mode"
on page 114). Measure the offset value at
low fire and compare it to the values in Table
3. If the offset value is out of range, the gas
valve set screw will need to be adjusted.
If adjustment is necessary, locate the set
screw as shown in Figure 10. Using a
or 4 mm Allen wrench, turn the set screw
no more than
/
turn clockwise to raise or
1
4
counterclockwise to lower the offset value.
Figure 10
The set screw is located behind
Note
the screw-on cover. This must be
removed first.
d. At high fire, do not check the offset value
and never adjust the gas valve.
WARNING
Improper gas valve settings can cause fire or
explosion and result in death, serious injury or
property damage.
114 Appendixes
13. Once the CO
confirmed, apply the included conversion stickers
to show that the appliance has been converted
to natural gas. Place this labels adjacent to the
rating plate as shown in Figure 11.
Cet appareil a ete converti au Gaz Naturel
Ori ce Size / Injecteur:
Inlet Gas Pressure / Pression d'entrée du gaz:
/
in.
5
32
Manifold Gas Pressure /
BTU Input / Debit calori que:
Figure 11. Proper Placement of Gas Conversion Labels
Note
Setting the Operation Mode
1. Press and hold the Menu button (
Back button (
and then select 4. Special Operations.
2. Press the Up button (
(
) to switch between the special operation
modes. Press the OK button (
parameter or to run a special operation mode.
Item
1. Normal
2. 1
MIN
st
3. 1
MAX
st
4. 2
MIN
nd
5. 2
MAX
nd
3. Press the Back button (
previous screen or menu.
or offset values have been
2
This unit has been
This unit has been
Converted to Natural Gas /
Converted to Propane fuel /
Cet appareil a ete converti au Propane
Ori ce Size / Injecteur:
Min. 4.8 mm to Max. 7.5 mm
Min. 3.9 mm to Max. 5.65 mm
Inlet Gas Pressure / Pression d'entrée du gaz:
Min. 3.5 to Max. 10.5 inches WC
Min. 8.0 to Max. 13.0 inches WC
Manifold Gas Pressure /
Pression à la tubulure d'alimentation:
Pression à la tubulure d'alimentation:
Min. -0.03 to Max. -0.96 inches WC
Min. -0.02 to Max. -0.96 inches WC
BTU Input / Debit calori que:
Max. 199,900 BTUh - Min. 13,300 BTUh
Max. 199,900 BTUh - Min. 13,300 BTUh
Conversion Kit No.: NAC-N240
Conversion Kit No.: NAC-L240
This water heater was converted on
______/______/______ to ____________ gas
with Kit No. ________________________
by _________________________________
_________________________________
(name and address of organization making
this conversion, who accepts responsibility
for the correctness of this conversion)
Manifold Gas Pressure ratings can
change due to updated orifice
sizes. Please confirm new manifold
pressures approved by CSA before
production of gas conversion labels.
) simultaneously for 3 seconds
) or the Down button
Description
Set the water heater to run in the
normal mode.
Set the water heater to run in
the 1-stage minimum operation
mode.
Set the water heater to run in
the 1-stage maximum operation
mode.
Set the water heater to run in
the 2-stage minimum operation
mode.
Set the water heater to run in
the 2-stage maximum operation
mode.
) to return to the