Siemens SIMATIC NET RUGGEDCOM RS900 Installation Manual page 44

Rugged ethernet switches
Hide thumbs Also See for SIMATIC NET RUGGEDCOM RS900:
Table of Contents

Advertisement

61000-4-29
IEC 60255-5
EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RS900 meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports. Class 1 allows for temporary communica-
tion loss, while Class 2 requires error-free and interrupted communications.
Fast Transient
Dielectric Strength
RUGGEDCOM RS900
Installation Manual, 02/2020, C79000-G8976-1024-10
Test
IEC
Voltage Dips and Interrupts
Dielectric Strength
HV Impulse
Description
ESD
Radiated RFI
Oscillatory
HV Impulse
6.2 EMC and Environmental Type Tests
Description
DC Pow-
er Ports
Signal Ports
DC Pow-
er Ports
AC Pow-
er Ports
Signal Ports
DC Pow-
er Ports
AC Pow-
er Ports
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Test Levels
30% for 0.1 s
60% for 0.1 s
100% for 0.05 s
2 kV (Failsafe Relay Output)
1.5 kV
2 kV
5 kV (Failsafe Relay Output)
5 kV
5 kV
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
2.5 kV Common Mode @ 1 MHz
2.5 kV Common and Dif-
ferential Mode @ 1 MHz
2.5 kV Common and Dif-
ferential Mode @ 1 MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kV (Failsafe Relay)
1.5 kV
2 kV
Certification
Severi-
ty Levels
 
 
 
 
 
 
 
35

Advertisement

Table of Contents
loading

Table of Contents