FORM 150.72-ICOM6
ISSUE DATE: 08/03/2022
TABLE 14 - YLAA FAULT AND INHIBIT CODES
CODE
TYPE
2
Unit Fault
4
Unit Fault
27
Unit Fault
28
Unit Fault
29
Unit Fault
31
Unit Fault
5
System Fault
7
System Fault
18
System Fault
19
System Fault
23
System Fault
24
System Fault
25
System Fault
26
System Inhibit
TABLE 15 - LEGEND
TYPE
3X
Automatically restarts on the first and second fault with a lockout on the third fault in 90 minutes
1X
Locks out on the first fault
AUTO
Allows restart once meeting the required conditions
JOHNSON CONTROLS
FAULT OR INHIBIT DESCRIPTION
Low Ambient Temperature
Low Leaving Chilled Liquid Temperature
Pump Trip (Hydro Pumps 1 or Hydro Pumps 2)
Pump Flow Failure (Hydro Pumps 1 or Hydro Pumps 2)
High Ambient Temperature
Flow Switch Open
High Discharge Pressure (Software)
Low Suction Pressure
Motor Protector/High Pressure (Mechanical)
Low Evaporator Temperature (R407c Only - N/A Hp Heating Mode)
Low Suction Superheat (EEV)
Sensor Failure (EEV)
Discharge Inhibit (Heat Pump heating mode only)
Motor Protector/High Pressure Inhibit
DEFINITION
SECTION 7 – UNIT CONTROLS
AUTO, 1X, 3X
(SEE LEGEND)
Auto
Auto
Auto
1x
Auto
Auto
3x
3x
3x
3x
3x
1x
3x
Auto
131
7